Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1143610 |
05/11/2025 |
SSOS |
Type: Category 1 Spill; Pipe Structural Problem/Failure - Controls caused 1296 gallons of sewage to spill from Lateral Clean Out (Private) at Pet Smart to Drainage Conveyance System that discharges to surface water |
Other (specify below). Attached directive |
Violation |
A |
SSO |
1143214 |
05/02/2025 |
SSOS |
Type: Category 1 Spill; Root Intrusion,Fats, Oil and Grease (FOG) caused 3660 gallons of sewage to spill from Lateral Clean Out (Private) at Mesa Verde Drive to Drainage Conveyance System that discharges to surface water |
Adjusted Schedule/Method of Preventive Maintenance,Inspected Sewer Using CCTV to Determine Cause. 1. capturing and removing wastewater from the storm drain system, and
2. better field reporting of SSO information, and
3. training on reading City/County storm drain maps, and
4. adding County and City storm drain maps to the District GIS, and
5. adding City Storm Water Quality officer cell number to the notification list.
6. Added line segments to our Hot Spot list
|
Violation |
A |
SSO |
1133121 |
02/12/2024 |
SSOS |
Type: Category 1 Spill; Operator Error (specify below) caused 41 gallons of sewage to spill from Inside Building or Structure, Lateral Clean Out (Private) at MacArthur #135605 Sewer SSO to Drainage Conveyance System that discharges to surface water |
Other (specify below). Information associated with the upstream manufacturing business and related batch discarrge will be added to the GIS system related to the specific/impacted public sewer pipe. |
Violation |
A |
SSO |
1133120 |
12/27/2023 |
SSOS |
Type: Category 1 Spill; Debris-Rags, Debris-wipes/Non-disposables, Fats, Oil and Grease (FOG) caused 75 gallons of sewage to spill from Gravity Mainline at 1656 Iowa Spill to Drainage Conveyance System that discharges to surface water |
Adjusted Schedule/Method of Preventive Maintenance, Other (specify below). The District has reduced the cleaning interval from 1 year to 6 months as the sewer was previously cleaned about 6 month earlier. District also cleaned the entire sewer from upstream terminus to the point of discharge at a District pump station. |
Violation |
A |
SSO |
1133119 |
12/21/2023 |
SSOS |
Type: Category 1 Spill; Debris-Rags, Debris-wipes/Non-disposables caused 200 gallons of sewage to spill from Inside Building or Structure, Lateral Clean Out (Private), Other (specify below) at CMSD Sewer 150042 MacArthur SSO to Drainage Conveyance System that discharges to surface water, Street/Curb and Gutter (2 3), Surface Water |
Other (specify below). The District will send information literature about wipes and flushing only toilet paper, poo, and pee down the toilets. The District will also review the subject sewer in 9 months, instead of the normal 12-month cleaning schedule, to determine if enhanced cleaning is required. The subject sewer was cleaned about 10 months prior to the SSO. |
Violation |
A |
SSO |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|