Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1135041 |
09/04/2024 |
Order Conditions |
On July 16, the total dissolved solids measurement was 810 mg/L, exceeding the permit limit of 500 mg/L. |
None taken. |
Violation |
B |
eSMR |
1135040 |
08/21/2024 |
Order Conditions |
On July 16, the total dissolved solids measurement was 770 mg/L, exceeding the permit limit of 500 mg/L. |
None taken. |
Violation |
B |
eSMR |
1135039 |
07/16/2024 |
Order Conditions |
On July 16, the total dissolved solids measurement was 640 mg/L, exceeding the permit limit of 500 mg/L. |
None taken. |
Violation |
B |
eSMR |
1123539 |
11/07/2023 |
Order Conditions |
The secondary MCL for total dissolved solids at monitoring location REC-001, (TDS) is 500 mg/L. On November 7th the reported value for TDS at REC-001 was 890mg/L. |
None Taken. |
Violation |
B |
eSMR |
1123540 |
10/03/2023 |
Order Conditions |
The secondary MCL for total dissolved solids at monitoring location REC-001, (TDS) is 500 mg/L. On October 3rd the reported value for TDS at REC-001 was 800mg/L.
|
None Taken |
Violation |
B |
eSMR |
1121481 |
09/12/2023 |
Order Conditions |
The secondary MCL for total dissolved solids, (TDS) is 500 mg/L. The reported value for the sample taken on September 12th was 690 mg/L. |
None taken. |
Violation |
B |
eSMR |
1121480 |
08/22/2023 |
Order Conditions |
The secondary MCL for total dissolved solids, (TDS) is 500 mg/L. The reported value for the sample taken on August 22nd was 630 mg/L. |
None taken. |
Violation |
B |
eSMR |
1121479 |
07/24/2023 |
DMON |
The weekly collection of BOD and TSS samples was not performed during the week of the 24th. However, Coliform sampling was conducted, and all results were reported to be less than 2.0 mg/L. In the preceding and subsequent weeks, BOD samples were below 5 mg/L, and TSS samples remained comfortably within the acceptable limits. |
We held a staff meeting during which we addressed the frequency of sampling and established protocols to prevent any future instances of missed samples. |
Violation |
B |
eSMR |
1121478 |
07/18/2023 |
Order Conditions |
The secondary MCL for total dissolved solids, (TDS) is 500 mg/L. The reported value for the sample taken on July 18th was 570 mg/L. |
None taken. |
Violation |
B |
eSMR |
1115965 |
02/16/2023 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 5.6 mg/L and reported value was 8.1 mg/L at EFF-002. |
Maximized aeration to the East holding pond to aid in ammonia reduction. |
Violation |
B |
eSMR |
1112925 |
10/04/2022 |
Order Conditions |
The Total Dissolved Solids limit at monitoring location REC-001 is 500, the analysis of the sample taken on 10/04/2022 was 930. |
None Taken. |
Violation |
B |
eSMR |
1109746 |
09/06/2022 |
Order Conditions |
The secondary MCL for total dissolved solids, (TDS) is 500 mg/L. The reported value for the sample taken on September 6th was 940 mg/L. |
None Taken. |
Violation |
B |
eSMR |
1109745 |
07/16/2022 |
Order Conditions |
The secondary MCL for total dissolved solids, (TDS) is 500 mg/L. The reported value for the sample taken on August 16th was 880 mg/L. |
None Taken. |
Violation |
B |
eSMR |
1109744 |
07/12/2022 |
Order Conditions |
The secondary MCL for total dissolved solids, (TDS) is 500 mg/L. The reported value for the sample taken on July 12th was 820 mg/L. |
None Taken. |
Violation |
B |
eSMR |
1106526 |
06/15/2022 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 760 mg/L at REC-001. |
None Taken |
Violation |
B |
eSMR |
1106525 |
05/17/2022 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 700 mg/L at REC-001. |
None Taken |
Violation |
B |
eSMR |
1104169 |
05/03/2022 |
LREP |
Quarterly SMR ( MONRPT ) (Quarterly Recycled Water Rpt) report for Q1 2022 (2091672) was due on 02-MAY-22 |
|
Violation |
B |
Report |
1106527 |
04/21/2022 |
Order Conditions |
Total dissolved solids maximum limit is 500 mg/L and reported value was 630 mg/L at REC-001. |
None Taken |
Violation |
B |
eSMR |
1106014 |
03/23/2022 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 650 mg/L at REC-001 |
|
Violation |
B |
Report |
1100625 |
02/02/2022 |
LREP |
Quarterly SMR ( MONRPT ) (Quarterly Recycled Water Rpt) report for Q4 2021 (2091668) was due on 01-FEB-22 |
|
Violation |
B |
Report |
1106013 |
02/02/2022 |
Order Conditions |
- Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 620 mg/L at REC-001 |
|
Violation |
B |
Report |
1106012 |
08/10/2021 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 1100 mg/L at REC-001 |
|
Violation |
B |
Report |
1106011 |
07/27/2021 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 1100 mg/L at REC-001 |
|
Violation |
B |
Report |
1106226 |
06/16/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 9.3 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1106225 |
05/25/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1106224 |
05/12/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1106010 |
03/24/2021 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 790 mg/L at REC-001 |
|
Violation |
B |
Report |
1106008 |
11/04/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 930 mg/L at REC-001 |
|
Violation |
B |
Report |
1106009 |
10/07/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 1000mg/L at REC-001 |
|
Violation |
B |
Report |
1106007 |
09/09/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 940mg/L at REC-001 |
|
Violation |
B |
Report |
1106006 |
07/08/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 760 mg/L at REC-001 |
|
Violation |
B |
Report |
1106004 |
06/10/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 680 mg/L at REC-001 |
|
Violation |
B |
Report |
1106003 |
04/06/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 610 mg/L at REC-001 |
|
Violation |
B |
Report |
1106002 |
03/05/2020 |
CAT2 |
TCDD Equivalents Daily Maximum limit is .000000028 ug/L and reported value was .00000421 ug/L at EFF-002. |
|
Violation |
B |
Report |
1106001 |
03/02/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 640 mg/L at REC-001 |
|
Violation |
B |
Report |
1106000 |
02/19/2020 |
Order Conditions |
Total Dissolved Solids Maximum limit is 500 mg/L and reported value was 670 mg/L at REC-001 |
|
Violation |
B |
Report |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|