Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1141786 |
02/25/2025 |
Order Conditions |
Lysimeter RD1-01 vacuum pressure was under 70-80 centibars, both under the new
proposed sampling method and prior to the implementation of the new method.
Violates Board Order R6V-2016-0051, Waste Discharge Requirements, Section II.A.19. |
Water Board staff are actively working with discharger. Discharger was requested to submit a work plan for the repair or replacement of RD1-01 to be submitted by April 15, 2025. |
Violation |
B |
Inspection |
1140766 |
02/25/2025 |
UAUTHDISC |
Windblown litter outside of the fence along the east side of the property. Violates Board Order No. R6V-2016-0051, Waste Discharge Requirements, Section II. A. 5. |
Water Board staff are working with discharger. Discharger to submit photo documentation of cleanup by 3/15/25. Discharger submitted documentation showing that they installed additional measures to prevent offsite windblown litter. |
Violation |
B |
Inspection |
1131199 |
08/30/2023 |
GWAT |
Exceeded WQPS Calcium, Dichlorodifluoromethane, Hardness as CaCO3, Magnesium, Nitrogen, Nitrate (as N), Tetrachloroethene (PCE), and Trichlorofluoromethane. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls. |
Violation |
B |
Report |
1131200 |
08/28/2023 |
DMON |
Vacuum will be applied on the system pressure line for each lysimeter to 70-80 centibars for at least 24 hours. Provided records do not show that the proper pressurizing procedures were used prior to sampling. Violates Board Order R6V-2016-0051 MRP II.A.2.c. |
Water Board staff is working with the discharger to determine appropriate next steps. |
Violation |
B |
Report |
1131196 |
03/20/2023 |
GWAT |
Exceeded WQPS Alkalinity as CaCO3, Dichlorodifluoromethane, Tetrachloroethene (PCE), and Trichlorofluoromethane. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls. |
Violation |
B |
Report |
1131198 |
03/13/2023 |
DMON |
Vacuum will be applied on the system pressure line for each lysimeter to 70-80 centibars for at least 24 hours. Provided records do not show that the proper pressurizing procedures were used prior to sampling. Violates Board Order R6V-2016-0051 MRP II.A.2.c. |
Water Board staff is working with the discharger to determine appropriate next steps. |
Violation |
B |
Report |
1131194 |
09/15/2022 |
GWAT |
Exceeded WQPS Dichlorodifluoromethane, Nitrogen, Nitrate (as N), Tetrachloroethene (PCE), and Trichlorofluoromethane. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls. |
Violation |
B |
Report |
1131192 |
03/03/2022 |
GWAT |
Exceeded WQPS Arsenic, Beryllium, Copper, Dichlorodifluoromethane, Mercury, Nickel, Nitrogen, Nitrate (as N), Tetrachloroethene (PCE), Tin, and Trichlorofluoromethane. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls. |
Violation |
B |
Report |
1131193 |
02/15/2022 |
DMON |
Vacuum will be applied on the system pressure line for each lysimeter to 70-80 centibars for at least 24 hours. Provided records do not show that the proper pressurizing procedures were used prior to sampling. Violates Board Order R6V-2016-0051 MRP II.A.2.c. |
Water Board staff is working with the discharger to determine appropriate next steps. |
Violation |
B |
Report |
1131191 |
08/25/2021 |
DMON |
Lysimeter field sheet not included for the 2021 H2 monitoring period. Violates Board Order R6V-2016-0051 MRP II.A.2.c. |
Water Board staff is working with the discharger to determine appropriate next steps. |
Violation |
B |
Report |
1131190 |
08/25/2021 |
GWAT |
Exceeded WQPS Magnesium, Nitrogen, Nitrate (as N), Tetrachloroethene (PCE), and Trichlorofluoromethane. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls.
|
Violation |
B |
Report |
1131189 |
02/11/2021 |
DMON |
Vacuum will be applied on the system pressure line for each lysimeter to 70-80 centibars for at least 24 hours. Provided records do not show that the proper pressurizing procedures were used prior to sampling. Violates Board Order R6V-2016-0051 MRP II.A.2.c. |
Water Board staff is working with the discharger to determine appropriate next steps. |
Violation |
B |
Report |
1131188 |
02/11/2021 |
GWAT |
Exceeded WQPS Dichlorodifluoromethane, Tetrachloroethene (PCE), and Trichlorofluoromethane. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls. |
Violation |
B |
Report |
1131186 |
07/22/2020 |
GWAT |
Exceeded WQPS Chloride, Tetrachloroethene (PCE), and Total Dissolved Solids. Violates Board Order R6V-2016-0051 MRP I.C.1.a. |
Discharger remediating release with CAP and implementing land fill gas extraction and source controls.
|
Violation |
B |
Report |
1131187 |
07/21/2020 |
DMON |
Vacuum will be applied on the system pressure line for each lysimeter to 70-80 centibars for at least 24 hours. Provided records do not show that the proper pressurizing procedures were used prior to sampling. Violates Board Order R6V-2016-0051 MRP II.A.2.c. |
Water Board staff is working with the discharger to determine appropriate next steps. |
Violation |
B |
Report |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|