Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1130326 |
06/30/2024 |
DMON |
Did not test for ammonia. |
Reviewed permit with staff |
Violation |
U |
eSMR |
1125406 |
02/29/2024 |
DMON |
Sampling and testing for monthly BOD and TSS was not performed at INF-001. |
Review of permit and sampling schedule with staff. |
Violation |
U |
eSMR |
1121402 |
09/30/2023 |
DMON |
The 2X/Month BOD, TSS second sample and test was not performed. |
Review of the permit with the responsible staff. |
Violation |
U |
eSMR |
1116135 |
03/10/2023 |
OEV |
Flow Daily Maximum limit is 15000 GPD and reported value was 19335 GPD at EFF-001. |
There is a plan to replace the existing WWTP. |
Violation |
U |
eSMR |
1116134 |
03/09/2023 |
OEV |
Flow Daily Maximum limit is 15000 GPD and reported value was 16127 GPD at EFF-001. |
There is a plan to replace the existing WWTP. |
Violation |
U |
eSMR |
1113388 |
02/02/2023 |
LREP |
Annual SMR ( SLUDGE ) (MRP section X (Biosolids)) report for 2022 (2313263) was due on 01-FEB-23 |
|
Violation |
B |
Report |
1114047 |
01/01/2023 |
DMON |
There was no required sampling performed during ocean discharge for the month of JAN23. This was due to no access to the facility due to a landslide that blocked the roadway which leads to the facility. |
The RWQCB was advised of the inability to access the facility. |
Violation |
U |
eSMR |
1114048 |
01/01/2023 |
OEV |
Flow Daily Maximum limit is 15000 GPD and reported value was 15426 GPD at EFF-001. |
There are plans at this time to replace the existing facility. |
Violation |
U |
eSMR |
1111396 |
11/18/2022 |
DMON |
Settleable Solids sample not taken. |
Spoke with the individual responsible and their supervisor. |
Violation |
B |
eSMR |
1093435 |
08/06/2021 |
Order Conditions |
The limit of 15,000gpd was exceeded due to a pump failure the previous day. |
Pump was replaced. |
Violation |
B |
eSMR |
1091415 |
05/10/2021 |
DMON |
Suspected error in the 24 Hour Composite sampling. |
Reviewed sampling protocols. |
Violation |
B |
eSMR |
1086697 |
01/28/2021 |
OEV |
Flow Daily Maximum limit is 0.015 MGD and reported value was 0.022 MGD at EFF-001. |
N/A |
Violation |
B |
eSMR |
1086699 |
01/27/2021 |
OEV |
Flow Daily Maximum limit is 0.015 MGD and reported value was 0.021 MGD at EFF-001. |
N/A |
Violation |
B |
eSMR |
1086698 |
01/26/2021 |
Order Conditions |
Maximum Daily Flow exceeded 0.015MGD due to Historically Heavy Rainfall |
N/A |
Violation |
B |
eSMR |
1069740 |
12/10/2019 |
Order Conditions |
On 12/10/19 the M-002 BOD sample was 75mg/L. This is above the weekly average limit of 45mg/L. On 12/26/19 the M-002 BOD sample was 10. These combined put the monthly average at 42.5 mg/L which is above the limit of 30mg/L. On 12/18/19 the INF BOD sample was128mg/L making the per cent removal at 66.8% which is below the limit of 85%. |
The foam in the reactor which is causing poor settling in the clarifier is being treated with sodium hypochlorite. |
Violation |
B |
eSMR |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|