Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1144015 |
05/29/2025 |
Other Water Code Sections |
Failure to provide a report of waste discharge 180 days in advance of the discharge of waste is a violation of CWC Section 13376. |
Corrective actions explained in the letter sent June 2, 2025 letter provided in the Attachment section of this report along with DBCM ND results. To prevent this situation from happening again, 1. flush times have been adjusted to happen during daytime operation hours, 2. discussions have also been had with the contractors and engineers ensure proper valving at all times and 3. to expedite the installation of the new level monitoring devices to better able operators to detect high water levels in the EQ tank |
Violation |
B |
eSMR |
1144722 |
05/29/2025 |
Order Conditions |
Violation of R5-2025-0014 Discharge Prohibitions III.A |
|
Violation |
B |
Report |
1144723 |
05/29/2025 |
Order Conditions |
Violation of R5-2025-0014 Discharge Prohibitions III.B. |
|
Violation |
B |
Report |
1141520 |
02/28/2025 |
DMON |
lab error that missed the dichlorobromomethane sample |
Communication with lab to catch errors, resampled 3-4-25 |
Violation |
U |
eSMR |
1127302 |
04/18/2024 |
OEV |
pH Weekly Discharge limit is 8.5 SU and reported value was 8.6 SU at EFF-001. |
The piece of equipment that was taking that reading has been replaced due to reading high |
Violation |
U |
eSMR |
1111707 |
11/03/2022 |
DMON |
When we received the results from the laboratory for our monthly monitoring we noticed that they had neglected to report the Electrical Conductivity for RSW-002 |
A new sample was delivered to the lab were are awaiting the results. this report will be updated once they are received. |
Violation |
B |
eSMR |
1111706 |
11/03/2022 |
CAT2 |
Dichlorobromomethane Monthly Average limit is 3.3 ug/L and reported value was 3.6 ug/L at EFF-002. |
We moved the location of the injection of our dechlor to in inlet side of the waste pump. this allows the dechlor to be injected against a much lower pressure in the system resulting in the pump not having to work as hard for the same feed rate as before. |
Violation |
U |
eSMR |
1109297 |
10/02/2022 |
LREP |
Monthly SMR ( MONNPDES ) report for August 2022 (2378976) was due on 01-OCT-22 |
|
Violation |
B |
Report |
1111748 |
09/30/2022 |
CAT2 |
Dichlorobromomethane Monthly Average (Mean) limit is 3.3 ug/L and reported value was 3.67 ug/L at EFF-002. |
|
Violation |
B |
Report |
1111291 |
08/22/2022 |
Other Water Code Sections |
Failure to provide a report of waste discharge 180 days in advance of the discharge of aluminum sulfate is a violation of CWC Section 13376. |
|
Violation |
B |
Report |
1111289 |
08/22/2022 |
Order Conditions |
Violation of R5-2020-0016 Discharge Prohibition III.A. |
|
Violation |
B |
Report |
1111290 |
08/22/2022 |
Order Conditions |
Violation of R5-2020-0016 Discharge Prohibition III.B. |
|
Violation |
B |
Report |