Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1142205 |
03/05/2025 |
Order Conditions |
Daily maximum turbidity exceeded 10 NTU on 3/5, 3/6 and 3/7.
Daily average turbidity exceeded 2 NTU on 3/6, 3/7, and 3/8.
Turbidity exceeded 5 NTU more than 5% of the day on 3/5, 3/6, and 3/7.
Minimum hourly average UV transmittance was less than 55% on 3/5 and 3/6. |
Clear out filter influent pump station and clean filters/all backwash nozzles. |
Violation |
B |
eSMR |
1142208 |
03/03/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
Clean UV modules and ensure proper UV dosage is being maintained. |
Violation |
B |
eSMR |
1141656 |
02/28/2025 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 1.9 mg/L at EFF-001. |
Moved the recycle control gate back to it's proper position and replaced the sheared pin with a new one. Added a backup bolt incase the pin shears again. |
Violation |
B |
eSMR |
1141658 |
02/26/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
UV Dose is set to the maximum dose, used polymer to help everything settle in the secondary clarifier, and cleaned UV units after storms had passed. |
Violation |
B |
eSMR |
1141657 |
02/10/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 270.0 MPN/100 mL at EFF-001. |
UV Dose is set to the maximum dose, used polymer to help everything settle in the secondary clarifier, and cleaned UV units after storms had passed. |
Violation |
B |
eSMR |
1141662 |
02/05/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 270.0 MPN/100 mL at EFF-001. |
UV Dose is set to the maximum dose, used polymer to help everything settle in the secondary clarifier, and cleaned UV units after storms had passed. |
Violation |
B |
eSMR |
1143133 |
02/05/2025 |
OEV |
Total Coliform Single Sample Maximum limit is 240 MPN/100 mL and reported value was 570 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1141663 |
02/01/2025 |
Order Conditions |
Daily maximum turbidity exceeded the limit of 10 NTU on 2/1, 2/2, 2/12, and 2/13.
Daily average turbidity exceeded the limit of 2 NTU on 2/1 and 2/6.
Turbidity exceeded 5 NTU more than 5% of the day on 2/1, 2/2, 2/12, and 2/13.
Minimum hourly average UV transmittance was less than 55% on 2/1 and 2/5. |
Used polymer to help everything settle in the secondary clarifier and had all 3 filters running in hand while continuously backwashing. |
Violation |
B |
eSMR |
1143132 |
01/31/2025 |
CAT1 |
Ammonia, Total (as N) Monthly Average (Mean) limit is 1.6 mg/L and reported value was 1.8 mg/L at EFF-001. |
|
Violation |
B |
Report |
1140666 |
01/04/2025 |
CAT1 |
Ammonia, Total (as N) Weekly Average (Mean) limit is 3.6 mg/L and reported value was 4.3 mg/L at EFF-001. |
Allow the plant to recover by pumping out the second oxidation ditch. |
Violation |
B |
eSMR |
1139108 |
12/31/2024 |
CAT1 |
Ammonia, Total (as N) Monthly Average (Mean) limit is 1.6 mg/L and reported value was 3.4 mg/L at EFF-001. |
Allow the plant to recover by pumping out the second oxidation ditch. |
Violation |
B |
eSMR |
1139107 |
12/28/2024 |
CAT1 |
Ammonia, Total (as N) Weekly Average (Mean) limit is 3.6 mg/L and reported value was 3.8 mg/L at EFF-001. |
Allow the plant to recover by pumping out the second oxidation ditch. |
Violation |
B |
eSMR |
1140131 |
12/23/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1139106 |
12/21/2024 |
CAT1 |
Ammonia, Total (as N) Weekly Average (Mean) limit is 3.6 mg/L and reported value was 8.7 mg/L at EFF-001. |
Allow the plant to recover by pumping out the second oxidation ditch. |
Violation |
B |
eSMR |
1140130 |
12/19/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 122.2 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1139109 |
12/15/2024 |
Order Conditions |
Minimum hourly UV transmittance was below 55% on 12/15, 12/16, 12/17, 12/24, and 12/26.
Daily average turbidity at FIL-001 exceeded 2 NTU on 12/16, 12/17, and 12/18.
Turbidity at FIL-001 exceeded 5 NTU more than 5% of the day on 12/18 and 12/19.
|
Allow the plant to recover by pumping out the second oxidation ditch. |
Violation |
B |
eSMR |
1138255 |
11/21/2024 |
Order Conditions |
Daily maximum turbidity exceeded 10 NTU on 11/21, 11/22, and 11/23.
Daily average turbidity exceeded 2 NTU on 11/23.
Turbidity exceeded 5 NTU more than 5% of the day on 11/21, 11/22, and 11/23.
Minimum hourly UV transmittance was below 55% on 11/23.
|
UV Dose was increased, shaved as much influent flow to the oxidation ditch that was offline, and used polymer to help everything settle in the secondary clarifier. |
Violation |
B |
eSMR |
1136155 |
10/21/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
Change out sampling lines. |
Violation |
B |
eSMR |
1136154 |
10/17/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 6.1 MPN/100 mL at EFF-001. |
Change out sampling lines. |
Violation |
B |
eSMR |
1136156 |
10/16/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 7.8 MPN/100 mL at EFF-001. |
Change out sampling lines. |
Violation |
B |
eSMR |
1132861 |
08/26/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 11.5 MPN/100 mL at EFF-001. |
Once the new Gate Drill arrives a full UV and channel cleaning will be performed. |
Violation |
B |
eSMR |
1136152 |
08/22/2024 |
Order Conditions |
Turbidity at FIL-001 exceeded 5 NTU for more than 5 % of the day during 8/22/2024. |
|
Violation |
B |
Report |
1132863 |
08/21/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 11.5 MPN/100 mL at EFF-001. |
Once the new Gate Drill arrives a full UV and channel cleaning will be performed. |
Violation |
B |
eSMR |
1132859 |
08/19/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.9 MPN/100 mL at EFF-001. |
Once the new Gate Drill arrives a full UV and channel cleaning will be performed. |
Violation |
B |
eSMR |
1132864 |
08/14/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.9 MPN/100 mL at EFF-001. |
Once the new Gate Drill arrives a full UV and channel cleaning will be performed. |
Violation |
B |
eSMR |
1129806 |
06/13/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 16.5 MPN/100 mL at EFF-001. |
Staff is working on replacing UV mods with new quartz jackets and new lamps. |
Violation |
B |
eSMR |
1129809 |
06/12/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 19.5 MPN/100 mL at EFF-001. |
Staff is working on replacing UV mods with new quartz jackets and new lamps. |
Violation |
B |
eSMR |
1129808 |
06/06/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 5.8 MPN/100 mL at EFF-001. |
Staff is working on replacing UV mods with new quartz jackets and new lamps. |
Violation |
B |
eSMR |
1129807 |
06/05/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 2.7 MPN/100 mL at EFF-001. |
Staff is working on replacing UV mods with new quartz jackets and new lamps. |
Violation |
B |
eSMR |
1130434 |
05/15/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.6 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1128965 |
05/13/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.6 MPN/100 mL at EFF-001. |
Staff is working on replacing UV mods with new quartz jackets and new lamps. |
Violation |
B |
eSMR |
1127801 |
04/17/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
Staff cleaned the UV system |
Violation |
B |
eSMR |
1125988 |
03/21/2024 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 NTU at FIL-002. |
Verify Dissolved oxygen reading on SCADA matches what the meter is reading at the oxidation ditch. |
Violation |
B |
eSMR |
1125294 |
02/05/2024 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU and reported value was 3 on 2/5 and 3 on 2/6. |
UV Dose was increased, shaved as much influent flow to the oxidation ditch that was offline, and used polymer to help everything settle in the secondary clarifier. |
Violation |
B |
eSMR |
1127997 |
02/04/2024 |
Order Conditions |
Filter effluent turbidity exceeded 5 NTU for more than 5% of the day on 2/4. |
|
Violation |
B |
Report |
1125290 |
02/04/2024 |
Order Conditions |
Turbidity Daily Maximum limit is 10 NTU and reported value was 13 NTU at FIL-002. |
UV Dose was increased, shaved as much influent flow to the oxidation ditch that was offline, and used polymer to help everything settle in the secondary clarifier. |
Violation |
B |
eSMR |
1125291 |
02/01/2024 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55% and reported value was 51% on 2/1, 53% on 2/2, 45% on 2/4, 45% on 2/5, 49% on 2/6, 56% on 2/7, 48% on 2/19, and 50% on 2/20. |
UV Dose was increased, shaved as much influent flow to the oxidation ditch that was offline, and used polymer to help everything settle in the secondary clarifier. |
Violation |
B |
eSMR |
1124549 |
01/22/2024 |
DMON |
Discharger did not monitor pH, temperature, DO, or EC, or record visual observations, on 1/22 for the month of January and the week ending 1/27. |
An SOP is being created for collecting RSW-001 samples so future sampling will not be missed. |
Violation |
B |
eSMR |
1127996 |
01/22/2024 |
Order Conditions |
Filter effluent turbidity exceed 5 NTU for more than 5% of the day on 1/22, 1/23, and 1/25. |
|
Violation |
B |
Report |
1124556 |
01/22/2024 |
Order Conditions |
Turbidity Daily Average (Mean) limit is 2 NTU at FIL-002, and reported value was 4 on 1/22, 5 on 1/23, 3 on 1/24, and 3 on 1/25. |
UV Dose was increased, shaved as much influent flow to the oxidation ditch that was offline, shaved as much flow as possible to the FEB, and used polymer to help everything settle in the secondary clarifier. |
Violation |
B |
eSMR |
1124551 |
01/22/2024 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55%, and reported value was 42 on 1/22, 42 on 1/23, 52 on 1/24, and 46 on 1/25. |
UV Dose was increased, shaved as much influent flow to the oxidation ditch that was offline, and used polymer to help everything settle in the secondary clarifier. |
Violation |
B |
eSMR |
1117239 |
03/31/2023 |
Deficient Reporting |
The Discharger did not conduct quarterly characterization, pyrethroid pesticide, and water column toxicity monitoring as required in the WDRs. |
|
Violation |
B |
Report |
1113916 |
01/17/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 54 %. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113913 |
01/16/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 50.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113919 |
01/15/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 48.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113921 |
01/14/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 49.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113910 |
01/13/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 54.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113909 |
01/12/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 51.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113918 |
01/11/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 50.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113917 |
01/10/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 48.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113914 |
01/09/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 49.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113911 |
01/06/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 54.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113912 |
01/05/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55.0 % and reported value was 51.0 % at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113923 |
01/03/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55% and reported value was 49% at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113922 |
01/02/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55% and reported value was 50% at FIL-002. |
UV dosage was turn up to compensate for the low transmittance |
Violation |
B |
eSMR |
1113915 |
01/01/2023 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 47 % at FIL-002. |
UV dosage was turned up to compensate for the low transmittance |
Violation |
B |
eSMR |
1112820 |
12/31/2022 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55% and reported value was 52% at UVS-001. |
raised UV dosage to compensate |
Violation |
B |
eSMR |
1111494 |
11/23/2022 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.1 MPN/100 mL at EFF-001. |
Cleaned system |
Violation |
B |
eSMR |
1110533 |
09/30/2022 |
DMON |
Discharger did not conduct water column toxicity monitoring with characterization monitoring during Q3 2022, as required in the MRP. |
|
Violation |
B |
Report |
1108806 |
08/10/2022 |
OEV |
Total Coliform 7-Day Median limit is 02.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
This year the District has been getting more often than usual, low level Bacti hits, it is possible this may be occurring because of the age of the UV system. So the District has purchased 12 new complete modules to help alleviate this possible problem. At a cost to the district of over $400,000 dollars. All 12 units have been installed as of August 29th 2022. |
Violation |
B |
eSMR |
1108808 |
08/03/2022 |
OEV |
Total Coliform 7-Day Median limit is 02.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
This year the District has been getting more often than usual, low level Bacti hits, it is possible this may be occurring because of the age of the UV system. So the District has purchased 12 new complete modules to help alleviate this possible problem. At a cost to the district of over $400,000 dollars. All 12 units have been installed as of August 29th 2022. |
Violation |
B |
eSMR |
1101194 |
01/12/2022 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.0 MPN/100 mL at EFF-001. |
The exceedance was a 4 MPN limit is 2.2. Looking at all of the UV data unsure of what the problem could have been. The system was cleaned on 1/11/2022. |
Violation |
B |
eSMR |
1101196 |
01/08/2022 |
Order Conditions |
Turbidity exceeded 5 NTU for more than 5% of the day at FIL-002. |
To fix this from happening again the Operators have been informed to not empty the secondary clarifiers by pumping the water back into the launders but back to the closet manhole which will take it back to the headworks to be retreated.
See cover letter |
Violation |
B |
eSMR |
1101197 |
01/08/2022 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55% and reported value was 46% at UVS-001. |
To fix this from happening again the Operators have been informed to not empty the secondary clarifiers by pumping the water back into the launders but back to the closet manhole which will take it back to the headworks to be retreated.
ATT&T was called to see what the problem was. AT&T checked to see if it was something they could fix there. It wasn't, AT&T said they would have to send someone out to fix the line. Work Order # PE4X4317 was implemented to fix the problem.
Also the District has contacted Jacobs Engineering to update our call out system and add an additional safety alarm that will call out if the Win 911 callout system should fail. Attached in attachments in the eSMR is the Jacobs email discussing the work to be done. |
Violation |
B |
eSMR |
1099804 |
12/30/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 54 % at UVS-001. |
Try to slow down flow more to secondary clarifier for better stability to achieve cleaner water to the filters. |
Violation |
B |
eSMR |
1099797 |
12/27/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 52 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099802 |
12/26/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 52 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099793 |
12/25/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 53 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099796 |
12/24/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 51 % at UVS-001. |
. The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099795 |
12/23/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 52 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099794 |
12/20/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.3 MPN/100 mL at EFF-001. |
Unsure of the cause all UV data numbers looked good. |
Violation |
B |
eSMR |
1099803 |
12/17/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 50 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099799 |
12/16/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 49 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099801 |
12/15/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 52 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1099800 |
12/14/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 49 % at UVS-001. |
The dosage set point was raised 10,000 uws/mc2 to compensate for the low UVT. |
Violation |
B |
eSMR |
1097322 |
10/27/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 53 % at UVS-001. |
everything was done that could be done to help prevent the exceedance. |
Violation |
B |
eSMR |
1097320 |
10/26/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 47.7 % at UVS-001. |
Everything was done that could be done to prevent the exceedance. |
Violation |
B |
eSMR |
1097321 |
10/25/2021 |
Order Conditions |
UV Transmittance 1-Hour Average (Mean) limit is 55 % and reported value was 46.8 % at UVS-001. |
Everything was done that could be done to prevent the exceedance. |
Violation |
B |
eSMR |
1097347 |
08/12/2021 |
Surface Water |
Dissolved Oxygen Daily Minimum limit is 7.0 mg/L and reported value was 1.2 mg/L at RSW-002. |
Asked Yuba County to clean out channel of plant growth |
Violation |
B |
eSMR |
1097346 |
07/16/2021 |
Surface Water |
Dissolved Oxygen Instantaneous Minimum limit is 7.0 mg/L and reported value was 2.2 mg/L at RSW-002. |
Ask Yuba County to clean out channel |
Violation |
B |
eSMR |
1092683 |
06/15/2021 |
OEV |
Total Coliform Instantaneous Maximum limit is 240 MPN/100 mL and reported value was 540 MPN/100 mL at EFF-001. |
Lab Director will be giving proper instructions on how to sterilize testing equipment and sample Bacties properly. |
Violation |
B |
eSMR |
1097341 |
06/10/2021 |
Surface Water |
Dissolved Oxygen Instantaneous Minimum limit is 7.0 mg/L and reported value was 6.8 mg/L at RSW-002. |
Ask Yuba County to clean ditch |
Violation |
B |
eSMR |
1091568 |
05/27/2021 |
Surface Water |
Receiving water limitation for DO is 7.0 mg/L at any time, and discharger reported 6.9 mg/L at RSW-002 on 5/27/2021. |
|
Violation |
B |
Report |
1091508 |
05/26/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 17.5 MPN/100 mL at EFF-001. |
Cleaned sampling equipment |
Violation |
B |
eSMR |
1091567 |
05/03/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.3 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1088205 |
02/24/2021 |
Order Conditions |
Turbidity Daily Maximum limit is 10 NTU and reported value was 15 NTU at FIL-002. |
This was only at the Filters and lasted for around seven minutes. The Effluent NTU never exceeded 3.8 NTU and the UV transmittance never dipped below 59 and the dosage on channel one minimum was 106,000 and Channel two was 111,000. |
Violation |
B |
eSMR |
1080838 |
09/08/2020 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.9 MPN/100 mL at EFF-001. |
Cleaned UV system to help to make sure the system is running efficiently. |
Violation |
B |
eSMR |
1080837 |
09/02/2020 |
Order Conditions |
Turbidity Daily Maximum limit is 10 NTU and reported value was 11.7 NTU at FIL-001. |
Changes to the S.C.A.D.A. alarm system and new programing has been put in place to help to prevent this in the future. |
Violation |
B |
eSMR |
1079902 |
08/13/2020 |
Order Conditions |
Daily maximum turbidity at FIL-001 exceeded the WDR limit (10 NTU) on 8/13 (15 NTU).
Daily average turbidity at FIL-001 exceeded the WDR limit (2 NTU) on 8/13 (3 NTU).
Turbidity at FIL-001 exceeded 5 NTU more than 5% of the time on 8/13 and 8/14.
Hourly average UV transmittance was less than 55% during 02:00-03:00, 03:00-04:00, 05:00-06:00, 07:00-08:00 on 8/13. |
reprogramed alarm system to allow Operator and or UV transmittance system to shut down system and divert flow |
Violation |
B |
eSMR |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|