| 1143692 |
12/31/2024 |
Order Conditions |
During the third quarter 2024 groundwater monitoring event, total coliform organisms were reported in groundwater monitoring well MW-4 at 4 MPN/100mL. |
|
Violation |
B |
Report |
| 1143669 |
11/30/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the 30-day average BOD concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 40 mg/L. The November 2024 monitoring report indicates that the 30-day average BOD effluent concentration was 65.3 mg/L. |
|
Violation |
B |
Report |
| 1143676 |
11/30/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the November 2024 monitoring, total coliform was reported at 801 MPN/100 mL. |
|
Violation |
B |
Report |
| 1143689 |
11/30/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the November 2024 monitoring was greater than 8.5 pH units on 5 November 2024. |
|
Violation |
B |
Report |
| 1143682 |
11/06/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the daily maximum Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 230 mg/L. Total coliform was reported at 1600 MPN/100 mL on 23 October 2024. |
|
Violation |
B |
Report |
| 1143675 |
10/31/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the October 2024 monitoring, total coliform was reported at 418.45 MPN/100 mL. |
|
Violation |
B |
Report |
| 1143688 |
10/31/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the October 2024 monitoring was greater than 8.5 pH units on 1 October 2024. |
|
Violation |
B |
Report |
| 1143681 |
10/23/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the daily maximum Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 230 mg/L. Total coliform was reported at 1600 MPN/100 mL on 23 October 2024. |
|
Violation |
B |
Report |
| 1143691 |
09/30/2024 |
Order Conditions |
During the third quarter 2024 groundwater monitoring event, total coliform organisms were reported in groundwater monitoring well MW-4 at 33 MPN/100mL. |
|
Violation |
B |
Report |
| 1143674 |
08/31/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the August 2024 monitoring, total coliform was reported at 59.78 MPN/100 mL. |
|
Violation |
B |
Report |
| 1143687 |
08/31/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the August 2024 monitoring was greater than 8.5 pH units on 13 August 2024, 20 August 2024 and 29 August 2024. |
|
Violation |
B |
Report |
| 1143668 |
07/31/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the 30-day average BOD concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 40 mg/L. The July 2024 monitoring report indicates that the 30-day average BOD effluent concentration was 50.8 mg/L. |
|
Violation |
B |
Report |
| 1143673 |
07/31/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the July 2024 monitoring, total coliform was reported at 470.9 MPN/100 mL. |
|
Violation |
B |
Report |
| 1143686 |
07/31/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the July 2024 monitoring was greater than 8.5 pH units on 10 July 2024, 17 July 2024 and 23 July 2024. |
|
Violation |
B |
Report |
| 1143680 |
07/17/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the daily maximum Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 230 mg/L. Total coliform was reported at 280 MPN/100 mL on 17 July 2024. |
|
Violation |
B |
Report |
| 1143679 |
07/02/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the daily maximum Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 230 mg/L. Total coliform was reported at 1600 MPN/100 mL on 2 July 2024. |
|
Violation |
B |
Report |
| 1143672 |
06/30/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the June 2024 monitoring, total coliform was reported at 536.58 MPN/100 mL. |
|
Violation |
B |
Report |
| 1143685 |
06/30/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the June 2024 monitoring was greater than 8.5 pH units on 5 June 2024 and 14 June 2024. |
|
Violation |
B |
Report |
| 1143678 |
06/26/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the daily maximum Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 230 mg/L. Total coliform was reported at 540 MPN/100 mL on 26 June 2024. |
|
Violation |
B |
Report |
| 1143677 |
06/20/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the daily maximum Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 230 mg/L. Total coliform was reported at 1600 MPN/100 mL on 20 June 2024. |
|
Violation |
B |
Report |
| 1143671 |
05/31/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the May 2024 monitoring, total coliform was reported at 191.68 MPN/100 mL. |
|
Violation |
B |
Report |
| 1143684 |
05/31/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the May 2024 monitoring was greater than 8.5 pH units on 3 May 2024, 8 May 2024, 15 May 2024 and 22 May 2024. |
|
Violation |
B |
Report |
| 1143683 |
04/30/2024 |
Order Conditions |
Discharge Specification B.6 of the WDRs states: “The discharge shall not have a pH less than 6.5 nor greater than 8.5.” The reported pH in the discharge during the April 2024 monitoring was greater than 8.5 pH units on 17 April 2024 and 29 April 2024.. |
|
Violation |
B |
Report |
| 1143690 |
03/31/2024 |
Order Conditions |
During the first quarter 2024 groundwater monitoring event, total coliform organisms were reported in groundwater monitoring wells, MWs 3 and 4 at 6.8 and 79 MPN/100mL. |
|
Violation |
B |
Report |
| 1143670 |
02/29/2024 |
Order Conditions |
Discharge Specification B.4 of the WDRs states that the monthly median Total Coliform concentration of wastewater that is discharged to the effluent storage reservoir shall not exceed 23 MPN/100 mL. During the February 2024 monitoring, total coliform was reported at 33.9 MPN/100 mL. |
|
Violation |
B |
Report |
| 1108379 |
06/30/2022 |
Order Conditions |
Total coliform organisms reported at 17 MPN/100 mL in MW-4 during the second quarter 2022 monitoring event. |
|
Violation |
B |
Report |
| 1108378 |
03/31/2022 |
Order Conditions |
Total coliform organisms reported at 4.5 MPN/100 mL in MW-4 during the first quarter 2022 monitoring event. |
|
Violation |
B |
Report |
| 1108377 |
09/30/2021 |
Order Conditions |
Total coliform organisms reported at 4.5 MPN/100 mL in MW-4 during the third quarter 2021 monitoring event. |
|
Violation |
B |
Report |
|