Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1128051 |
04/26/2024 |
Order Conditions |
The daily average turbidity is 2 NTU, and daily average turbidity was 3 NTU on 4/26, 3 NTU on 4/27, 3 NTU on 4/28, and was 3 NTU on 4/29. |
Cleaned secondary clarifier weirs. |
Violation |
B |
eSMR |
1127951 |
03/31/2024 |
Deficient Reporting |
Discharger did not report quarterly arsenic or nitrogen at GW-001, GW-002, and GW-003. |
|
Violation |
B |
Report |
1127943 |
03/26/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-002. |
|
Violation |
B |
Report |
1126493 |
03/22/2024 |
Order Conditions |
Turbidity Daily Maximum limit is 10 NTU and reported value was 18.9 NTU at FIL-001. |
The 4 filters were taken offline and we are doing manual backwashes on the remaining 2 filters once a day. The date of the occurence, solids were heavy and some were released during a manual backwash. We have gone over the backwash sequence with all staff to ensure they wait the proper time, before putting the unit back in filtering mode. |
Violation |
B |
eSMR |
1126490 |
03/21/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 350.0 MPN/100 mL at EFF-002. |
Damaged filters have been taken offline and chlorine contact basin was pumped and cleaned. Large amount of solids in bottom of basin were removed. |
Violation |
B |
eSMR |
1126497 |
03/20/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 350 MPN/100 mL at EFF-002. |
Damaged filters have been taken offline and chlorine contact basin was pumped and cleaned. Large amount of solids in bottom of basin were removed. |
Violation |
B |
eSMR |
1126492 |
03/20/2024 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23.0 MPN/100 mL and reported value was 920 MPN/100 mL at EFF-002. |
Damaged filters have been taken offline and chlorine contact basin was pumped and cleaned. Large amount of solids in bottom of basin were removed. |
Violation |
B |
eSMR |
1126495 |
03/20/2024 |
OEV |
Total Coliform Single Sample Maximum limit is 240 MPN/100 mL and reported value was 920.0 MPN/100 mL at EFF-002. |
Damaged filters have been taken offline and chlorine contact basin was pumped and cleaned. Large amount of solids in bottom of basin were removed. |
Violation |
B |
eSMR |
1126494 |
03/19/2024 |
OEV |
Total Coliform Instantaneous Maximum limit is 240.0 MPN/100 mL and reported value was 350.0 MPN/100 mL at EFF-002. |
Damaged filters have been taken offline and chlorine contact basin was pumped and cleaned. Large amount of solids in bottom of basin were removed. |
Violation |
B |
eSMR |
1121769 |
07/11/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
1121768 |
07/06/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 9.2 MPN/100 mL at EFF-002. |
|
Violation |
B |
Report |
1119793 |
07/05/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 9.2 MPN/100 mL at EFF-002. |
It was noted on 7/2 during morning rounds, that the contact basin had looked a little hazy. After investigation, we found that polymer was being slightly overdosed so we promptly made the necessary adjustments to the thickener system, which seem to have corrected the chlorine disinfection process. |
Violation |
B |
eSMR |
1119157 |
05/06/2023 |
OEV |
pH Instantaneous Minimum limit is 6.0 SU and reported value was 5.2 SU at EFF-002. |
|
Violation |
B |
Report |
1116009 |
03/31/2023 |
DMON |
Discharger did not report groundwater monitoring results for nitrogen at all three wells. |
Spoke to lab about maintaining proper QA/QC standards. |
Violation |
B |
eSMR |
1114633 |
01/05/2023 |
Order Conditions |
Daily average turbidity at FIL-001 was 3 NTU on 1/3 and 4 NTU on 1/5, and limit is 2 NTU,
Turbidity exceeded 5 NTU at FIL-001 more than 5% of the day on 1/5. |
|
Violation |
B |
Report |
1114632 |
12/15/2022 |
Order Conditions |
Daily average turbidity was 3 NTU at FIL-001, and limit is 2 NTU. |
|
Violation |
B |
Report |
1100204 |
11/12/2021 |
DMON |
Discharger did not monitor effluent flow at the required frequency during 11/12/21 and 11/15/21. |
|
Violation |
B |
Report |
1089589 |
03/25/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at EFF-002. |
Please see cover letter |
Violation |
B |
eSMR |
1089587 |
03/24/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 7.8 MPN/100 mL at EFF-002. |
Please see cover letter |
Violation |
B |
eSMR |
1089588 |
03/23/2021 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 7.8 MPN/100 mL at EFF-002. |
Please see cover letter |
Violation |
B |
eSMR |