| Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
| 1151685 |
01/16/2026 |
DMON |
Data loss was reported Feb 12 to SWRCB. |
Faulty equipment was replaced. |
Violation |
U |
eSMR |
| 1151686 |
01/13/2026 |
DMON |
INF-001 and EFF-001 BOD samples were not valid due to contamination at the contract lab. |
See contract lab letter in attachments |
Violation |
U |
eSMR |
| 1145813 |
03/21/2025 |
OEV |
pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.2 SU at EFF-001. |
|
Violation |
B |
Report |
| 1132929 |
08/27/2024 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23 MPN/100 mL and reported value was 130 MPN/100 mL at UVS-001. |
Replace leaking hydraulic hoses and clean UV Channel 1 with soap and water. Flush channel and place back in service. No total coliform effluent limit exceedances since doing so. |
Violation |
B |
eSMR |
| 1132928 |
08/17/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at UVS-001. |
Replace leaking hydraulic hoses and clean UV Channel 1 with soap and water. Flush channel and place back in service. No total coliform effluent limit exceedances since doing so. |
Violation |
B |
eSMR |
| 1132927 |
08/16/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at UVS-001. |
Replace leaking hydraulic hoses and clean UV Channel 1 with soap and water. Flush channel and place back in service. No total coliform effluent limit exceedances since doing so. |
Violation |
B |
eSMR |
| 1132926 |
08/15/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.5 MPN/100 mL at UVS-001. |
Replace leaking hydraulic hoses and clean UV Channel 1 with soap and water. Flush channel and place back in service. No total coliform effluent limit exceedances since doing so. |
Violation |
B |
eSMR |
| 1115014 |
02/28/2023 |
Deficient Reporting |
Acute Toxicity Sampling was collected by Ironhouse Staff and relinquished to the FGL Lab Courier on February 7, 2023 at 1350 hours. Subsequently the sample was relinquished several more times prior to being received by ABC Labs on February 7, 2023 at 1700 hours. Apparently a janitor accepted delivery of the sample after normal business hours, thus preventing the analysis from being completed within a normal hold time.
Ironhouse staff were notified of the error on March 14, 2023. Therefore, resampling could not be completed within the required monitoring period and no results were reported. |
The contract laboratories are aware of the error. A letter from the lab is attached. |
Violation |
U |
eSMR |
| 1113944 |
01/31/2023 |
OEV |
Electrical Conductivity @ 25 Deg. C Monthly Average (Mean) limit is 1505 umhos/cm and reported value was 1511.67 umhos/cm at EFF-001. |
Reduce Collections System I&I on Bethel Island via a grout repair project. Engineering design is complete. Construction project should be complete in 2023. |
Violation |
B |
eSMR |
| 1099270 |
12/31/2021 |
Order Conditions |
Facility Flow Meters were not calibrated in 2021. |
Flow meters were Calibrated on January 10, 2022. |
Violation |
U |
eSMR |
|
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|