Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1134949 |
10/01/2024 |
Order Conditions |
Boron, 25-month rolling median was above the permit limit of 0.5 mg/L the recorded value of .65 mg/L for MW #1, 0.55mg/L for MW#1S, 0.51 mg/L for MW#2, 0.51 mg/L for MW#2D, 0.53 mg/L for MW#2S, .52 mg/L for MW#4S. |
|
Violation |
B |
Report |
1134950 |
10/01/2024 |
Order Conditions |
Nitrogen, 25-month rolling median was above the permit limit of 10 mg/L the recorded value of 33.5 mg/L for MW #1, 36.5 mg/L for MW#2, 26.65 mg/L for MW#2S. |
|
Violation |
B |
Report |
1134948 |
10/01/2024 |
Order Conditions |
Sodium, 25-month rolling median was above the permit limit of 150 mg/L the recorded value is 171.5 mg/L. |
|
Violation |
B |
Report |
1134946 |
08/29/2024 |
Order Conditions |
All samples during monitoring period were over the effluent TSS 7-day and 30-day averages. |
|
Violation |
B |
Report |
1134953 |
08/22/2024 |
Order Conditions |
Failure to implement a contingency plan to prevent spills due to insufficient freeboard |
|
Violation |
B |
Inspection |
1134951 |
08/22/2024 |
Order Conditions |
Failure to maintain at least two feet of freeboard in the treatment pond |
|
Violation |
B |
Inspection |
1134952 |
08/22/2024 |
Order Conditions |
No permanent markers in some of the treatment ponds |
|
Violation |
B |
Inspection |
1134928 |
07/24/2024 |
Order Conditions |
Failure to maintain at least two feet of freeboard in Pond 1 through Pond 5. This was also violated in RIB 1, 3A, 3B, 4A, and 4B. |
|
Violation |
B |
Report |
1134947 |
07/10/2024 |
Order Conditions |
Failure to maintain a dissolved oxygen concentration of 1.0 milligrams per liter (mg/L) |
|
Violation |
B |
Report |
1130378 |
06/30/2024 |
Order Conditions |
Discharging above the 30-Day average of 100 pounds/acre/day for BOD. 30-Day average in June was 124.7 pounds/acre/day |
|
Violation |
B |
Report |
1130382 |
04/01/2024 |
Order Conditions |
All samples during monitoring period were over the effluent TSS 7-day and 30-day averages. |
|
Violation |
B |
Report |
1130383 |
04/01/2024 |
Order Conditions |
Freeboard was below the Instantaneous Minimum limit of 2ft on all days during the monitoring period. |
|
Violation |
B |
Report |
1127210 |
02/09/2024 |
Order Conditions |
Failure to maintain at least two feet of freeboard in Pond 1 through Pond 5 |
|
Violation |
B |
Report |
1127209 |
01/31/2024 |
Order Conditions |
Discharging above the 30-Day average of 100 pounds/acre/day for BOD |
|
Violation |
B |
Report |
1125841 |
09/01/2023 |
Order Conditions |
Discharging above the 30-Day average of 100 pounds/acre/day for BOD |
|
Violation |
B |
Report |
1125842 |
01/18/2023 |
Order Conditions |
Failure to maintain ground water quality objectives |
|
Violation |
B |
Report |
1125840 |
01/01/2023 |
Order Conditions |
Discharging above 30- and 7-day average effluent limits |
|
Violation |
B |
Report |
1125843 |
01/01/2023 |
Order Conditions |
Failure to maintain a dissolved oxygen concentration of 1.0 milligrams per liter (mg/L) |
|
Violation |
B |
Report |
1125839 |
01/01/2023 |
Order Conditions |
Failure to maintain at least two feet of freeboard in Pond 1 through Pond 5 |
|
Violation |
B |
Report |
1111132 |
06/29/2022 |
Order Conditions |
Pursuant to General Permit Section B.2. “Wastewater ponds must contain permanent markers indicating depth and freeboard.” As seen and discussed at the inspection, there are no permanent markers in some of the treatment ponds. Greenfield must install permanent freeboard markers and demonstrate compliance with photos emailed to Central Coast Water Board staff. |
|
Violation |
B |
Inspection |
1100820 |
10/01/2021 |
Order Conditions |
Sections B-9, B-13, B-16. "Treatment ponds and disposal ponds shall have a freeboard greater than two feet."
"Wastewater application to spray fields irrigation areas shall be managed to prevent ponding."
"Spray field irrigation areas shall be operated using a regular rotation from area to another shall occur at least weekly between application, irrigated areas shall be allowed to dry to approximately the field moisture condition of non-irrigation." |
|
Violation |
B |
Report |
1097550 |
07/01/2021 |
Order Conditions |
Sections B-13 and B-16 requires sprayfield irrigation areas to be rotated and allowed to dry completely between applications, but discharger is now using a land application system rather than a sprayfield system. |
|
Violation |
B |
Report |
1097549 |
07/01/2021 |
Order Conditions |
Treatment ponds shall have a freeboard greater than two feet. Freeboard condition violated almost every week for almost every pond (of 5) from Jul 1 to Sept 30 2021. |
|
Violation |
B |
Report |
1093330 |
06/29/2021 |
GWAT |
downgradient monitoring well 2S. sodium reported value is 152 mg/L (permitted max value: 150 mg/L) |
|
Violation |
B |
Report |
1093325 |
06/24/2021 |
GWAT |
Downgradient monitoring well 2D. Reported value of nitrate: 31.6 mg/L (max permitted concentration: 10 mg/L) |
|
Violation |
B |
Report |
1093326 |
06/24/2021 |
GWAT |
Measurement obtained from downgradient well 4S. Reported value of Nitrate: 18.2 mg/L (permitted max concentration is 10 mg/L) |
|
Violation |
B |
Report |
1093334 |
06/22/2021 |
Order Conditions |
Not using a spray field: "Wastewater application to spray irrigation areas shall be managed to prevent ponding" January thru June |
|
Violation |
B |
Report |
1093333 |
05/05/2021 |
Order Conditions |
Treatment ponds have freeboard less than 2 feet (1.5-1.9 ft). Permit says: "Treatment ponds should have a freeboard greater than 2 feet"
Range from 4/07/2021 to 6/25/2021 |
|
Violation |
B |
Report |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|