Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1122496 |
07/24/2023 |
OEV |
Total Coliform Maximum Daily (MDEL) limit is 240 MPN/100 mL and reported value was 1600 MPN/100 mL. |
As per client, Sampling was done during an irrigation period that raised the Coliform count. Close continued monitoring will be conducted. |
Violation |
B |
Report |
1121326 |
04/05/2023 |
CAT1 |
Fluoride, Total Single Sample Maximum limit is 2.0 mg/L and reported value was 9.6 mg/L. |
Email Jacobs ask for continued monitoring of MCL levels to keep within limits. 10/27/2023 |
Violation |
B |
Report |
1107283 |
03/29/2022 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23 MPN/100 mL and reported value was 79 MPN/100 mL. |
|
Violation |
B |
Report |
1098123 |
12/15/2021 |
UAUTHDISC |
OES Call (#21-7175) was made to report a 20,000-gallon spill due to a sewer main blockage. The spill occurred on 15 December 2021 caused by a combination of a heavy rain event and improper disposal of foreign materials on the sewer collections system such as ammo, grease, grit, sand, rags, clothing, tools and alike. Excess sewage was taken to the Fort Irwin Waste Water Treatment facility - ponds onsite and routed through the system. |
A vacuum truck was used to capture as much of the ponded sewage as possible. 16 feet of sewer line main was replaced with new 24-inch pipe. Disinfection was completed. Excess fluid collected has been run through the waste water treatment plant. One final corrective action is pending: disposal of contaminated soil (pending Army, CH2M Hill discussion on how to dispose of munitions found in the soil). |
Violation |
B |
Report |
1071468 |
11/06/2019 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 6 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071467 |
11/05/2019 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071465 |
11/04/2019 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071463 |
11/03/2019 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 8 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071449 |
11/03/2019 |
OEV |
Total Coliform Not to exceed a specific limit more than once within any 30-day period. limit is 23 MPN/100 mL and reported value was 240 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071461 |
11/02/2019 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 5 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071451 |
11/02/2019 |
OEV |
Total Coliform Single Sample Maximum limit is 240 MPN/100 mL and reported value was 1600 MPN/100 mL. |
Discharger did not propose or identify any corrective actions taken. |
Violation |
B |
Report |
1071444 |
10/18/2019 |
DMON |
Power outage did not allow reading of Influent water max flow readings. Violating board order 06-2004-005 MRP section I.A.4. |
Discharger did not propose nor identify any corrective actions taken. |
Violation |
B |
Report |
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|