| Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
| 1148376 |
09/23/2025 |
OEV |
Total Coliform Daily Maximum limit is 240 MPN/100 mL and reported value was 350 MPN/100 mL at EFF-001. |
None needed, it was an error somewhere in the sampling/lab process. All previous and follow-up bacti samples have been non-detect. |
Violation |
U |
eSMR |
| 1147220 |
08/19/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
The result for that day was ND but due to the 7-day median the result from the previous day was high so it causes multiple violations for the same sample. |
Violation |
U |
eSMR |
| 1147219 |
08/18/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
Extra precaution when handling any sampling bottle and also used an extra person to help shield from any elements until we can figure out real cause of random spike. |
Violation |
U |
eSMR |
| 1146300 |
07/29/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 5 MPN/100 mL at EFF-001. |
Extra careful with handling of bacti bottle, also did extra cleaning of the uv channel, visited the lab, inspected sampling location. |
Violation |
U |
eSMR |
| 1146302 |
07/28/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 10.5 MPN/100 mL at EFF-001. |
Extra careful with handling of bacti bottle, also did extra cleaning of the uv channel, visited the lab, inspected sampling location. |
Violation |
U |
eSMR |
| 1146301 |
07/24/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 10.5 MPN/100 mL at EFF-001. |
Extra careful with handling of bacti bottle, also did extra cleaning of the uv channel, visited the lab, inspected sampling location. |
Violation |
U |
eSMR |
| 1146299 |
07/23/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 13 MPN/100 mL at EFF-001. |
Extra careful with handling of bacti bottle, also did extra cleaning of the uv channel, visited the lab, inspected sampling location. |
Violation |
U |
eSMR |
| 1146303 |
07/15/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 11 MPN/100 mL at EFF-001. |
Extra careful with handling of bacti bottle, also did extra cleaning of the uv channel, visited the lab, inspected sampling location. |
Violation |
U |
eSMR |
| 1146298 |
07/14/2025 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 11 MPN/100 mL at EFF-001. |
Extra careful with handling of bacti bottle, also did extra cleaning of the uv channel, visited the lab, inspected sampling location. |
Violation |
U |
eSMR |
| 1130907 |
07/31/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 7.8 MPN/100 mL at EFF-001. |
We have been trying to time correctly and cover our sampling location as best we can but the farmers were out all day this week. |
Violation |
U |
eSMR |
| 1130906 |
07/30/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 7.8 MPN/100 mL at EFF-001. |
We have been doing our best to try to time our coliform sampling when the farmers aren't stirring up dust but they were doing it all day most of the week. |
Violation |
U |
eSMR |
| 1128089 |
04/15/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 36 MPN/100 mL at EFF-001. |
Notified the owner about the issue and that they need to cover it and informed all staff to be aware of issue while taking bacti samples. |
Violation |
U |
eSMR |
| 1124336 |
01/04/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
We have ongoing testing to figure out the cause of the two spikes, but so far seems to be nothing conclusive that could have caused it. |
Violation |
B |
eSMR |
| 1124337 |
01/03/2024 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4 MPN/100 mL at EFF-001. |
We have ongoing testing to figure out the cause of the two spikes, but so far seems to be nothing conclusive that could have caused it. |
Violation |
B |
eSMR |
| 1123364 |
11/16/2023 |
OEV |
Total Coliform Instantaneous Maximum limit is 240 MPN/100 mL and reported value was 350 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
| 1123363 |
06/12/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 33 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
| 1123362 |
06/07/2023 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 33 MPN/100 mL at EFF-001. |
|
Violation |
B |
Report |
| 1115425 |
03/22/2023 |
OEV |
pH Single Sample Maximum limit is 8.5 SU and reported value was 9.0 SU at EFF-001. |
We double checked with the pH coming from our water plants which is the main source of our flow and determined it was still in good range. We then discarded that pH probe immediately and also administered retraining for ALL staff on how to properly calibrate all pH probes and to do it daily to avoid ever having this mistake again. Also, we ordered a brand new pH buffer to ensure everything is new for calibrations. |
Violation |
B |
eSMR |
| 1115424 |
03/21/2023 |
OEV |
pH Single Sample Maximum limit is 8.5 SU and reported value was 8.9 SU at EFF-001. |
We double checked with the pH coming from our water plants which is the main source of our flow and determined it was still in good range. We then discarded that pH probe immediately and also administered retraining for ALL staff on how to properly calibrate all pH probes and to do it daily to avoid ever having this mistake again. Also, we ordered a brand new pH buffer to ensure everything is new for calibrations. |
Violation |
B |
eSMR |
| 1115423 |
03/15/2023 |
OEV |
pH Single Sample Maximum limit is 8.5 SU and reported value was 8.8 SU at EFF-001. |
We double checked with the pH coming from our water plants which is the main source of our flow and determined it was still in good range. We then discarded that pH probe immediately and also administered retraining for ALL staff on how to properly calibrate all pH probes and to do it daily to avoid ever having this mistake again. Also, we ordered a brand new pH buffer to ensure everything is new for calibrations. |
Violation |
U |
eSMR |
| 1115421 |
03/08/2023 |
OEV |
pH Single Sample Maximum limit is 8.5 SU and reported value was 8.9 SU at EFF-001. |
We double checked with the pH coming from our water plants which is the main source of our flow and determined it was still in good range. We then discarded that pH probe immediately and also administered retraining for ALL staff on how to properly calibrate all pH probes and to do it daily to avoid ever having this mistake again. Also, we ordered a brand new pH buffer to ensure everything is new for calibrations. |
Violation |
U |
eSMR |
| 1115422 |
03/01/2023 |
OEV |
pH Single Sample Maximum limit is 8.5 SU and reported value was 8.9 SU at EFF-001. |
We double checked with the pH coming from our water plants which is the main source of our flow and determined it was still in good range. We then discarded that pH probe immediately and also administered retraining for ALL staff on how to properly calibrate all pH probes and to do it daily to avoid ever having this mistake again. Also, we ordered a brand new pH buffer to ensure everything is new for calibrations. |
Violation |
U |
eSMR |
|
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
|