General Information
Region Place ID Place Name Place Type Place Address Place County
5F 214899 Clovis WWTF Wastewater Treatment Facility 9700 East Ashlan Clovis, CA, 93619 Fresno

Expand/Contract Related Parties
Related Parties
Party Party Type Party Name Role Classification Relationship Start Date Relationship End Date
571590 Person Paul Armendariz Is Onsite Manager For 11/07/2018
139421 Person Nicholas Torstensen Is A Data Submitter For 07/30/2018
573105 Person Bret Gordon Johnson Is A Data Submitter For 01/30/2018
571997 Person Scott Redelfs Is Onsite Manager For 01/25/2018
571590 Person Paul Armendariz Is A Data Submitter For 12/21/2017 03/05/2019
549194 Person Glenn L Eastes Is A Data Submitter For 11/21/2014 03/01/2018
8865 Organization Clovis City Owner City Agency 05/06/2010
55002 Person Lisa Koehn Is Onsite Manager For 02/25/2009 02/01/2018
393345 Person Robert Rush Is Onsite Manager For 02/25/2009
500501 Person Mike Leonardo Is Onsite Manager For 02/25/2009 01/24/2018
138727 Person Matt Scroggins Case Worker 11/19/2008
532251 Person Daniel Burns Is Onsite Manager For 03/14/2008 01/18/2013
55002 Person Lisa Koehn Responsibility For 01/03/2007 02/01/2018
Total Related Parties: 13

Expand/Contract Regulatory Measures
Regulatory Measures
Reg Measure ID Reg Measure Type Region Program Order No. WDID Effective Date Expiration Date Status Amended?
440393 Co-Permitee SB SLIC 2020-0015-DWQ 5C10NP00012 07/09/2020 Active N
429278 NPDES Permit 5F NPDMUNILRG R5-2019-0021 5C10NP00012 06/01/2019 05/31/2024 Active Y
390415 NPDES Permit 5F NPDMUNILRG R5-2014-0005 5C10NP00012 03/28/2014 03/01/2019 Historical N
379016 Letter 5F NPDESWW R5-2008-0036 5C10NP00012 05/10/2011 Historical N
173793 NPDES Permit 5F NPDMUNILRG R5-2008-0036 5C10NP00012 05/05/2008 05/01/2013 Historical N
Total Reg Measures: 5

Expand/Contract Violations
Violations
Violation ID Occurred Date Violation Type (-) Violation Description Corrective Action Status Classification Source
1126885 03/29/2024 DMON RW discharge started at 001 on March 22, 2024. Weekly field observations conducted on March 29, 2024 were inadvertently conducted at 002U/D instead of 001U/D. Discussed with staff and the following weekly field observation was conducted at the correct discharge point, 001U/D. Violation U eSMR
1126884 03/19/2024 OEV Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .76 NTU at FIL-001. The SOP on returning a membrane tank to normal filtration, as well as the permit limits, have been reviewed with the new operators. Violation U eSMR
1125395 02/23/2024 DMON TSS samples were collected and sent out to Moore Twining and Associates for analysis. The samples were not documented on the chain of custody, so the contract laboratory did not run the sample until after they were out of hold time. The results are documented on the SMR but out of hold time. Reviewed with operators and with lab. Violation U eSMR
1125394 02/06/2024 OEV Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .75 NTU at FIL-001. Programmer restored the 10 min re-circulation after a membrane tank has been in standby for 5 mins or more. It failed due to the outage on Jan 31, 2024. Violation U eSMR
1124429 02/02/2024 LREP Once Only OneTime ( TECHRPT ) (Q4 2023 (MRP VII.B.1 Recycled Water User Summary Report) report for 2023/10/01 (2816152) was due on 01-FEB-24 Violation B Report
1124737 01/31/2024 DMON The Clovis ST/WR Facility experienced a power outage on January 31st , 2024 causing the coliform incubator to fall below acceptable temperature. This makes the results for Coliform invalid on January 31st, 2024. Power restored Violation U eSMR
1123694 12/17/2023 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.49 SU at EFF-002. There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. Violation U eSMR
1123697 12/15/2023 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.4 SU at EFF-002. There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. Violation U eSMR
1123696 12/14/2023 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.44 SU at EFF-002. There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. Violation U eSMR
1123695 12/13/2023 OEV pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.43 SU at EFF-002. There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. Violation U eSMR
1109608 09/06/2022 DMON During the month of September 2022, we had our historian go down for a period of 6 days. We have been attempting to recover data from the PLC for dates 9/6-9/11/2022 but are unable to do so. The lost reportable data includes: UV Transmittance Average UV Transmittance Maximum UV Dose Average UV Dose Maximum We have alarm histories that are accurate as well as daily documented values for each one of these data points that have been reported. It would be a one-time read instead of a 24-hour max or average value. We have added an alarm into our SCADA call out system that will notify us if or when the historian goes down. In addition, We will be installing a stand-alone system as a backup to help prevent any future incidents of lost data. Violation U eSMR
1109607 09/06/2022 DMON During the month of September 2022, we had our historian go down for a period of 6 days. We have been attempting to recover data from the PLC for dates 9/6-9/11/2022 but are unable to do so. The lost reportable data includes: 1. Combined Filtrate Tubidity Maximum 2. Combined Filtrate Tubidity Average We have alarm histories that are accurate as well as daily documented values for each one of these data points that have been reported. It would be a one-time read instead of a 24-hour max or average value. We have added an alarm into our SCADA call out system that will notify us if or when the historian goes down. In addition, we will be installing a stand-alone system as a backup to help prevent any future incidents of lost data. Violation U eSMR
1107793 07/31/2022 CAT1 Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 5.65 mg/L at EFF-A. . Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February. Violation U eSMR
1107794 07/31/2022 CAT1 Ammonia, Total (as N) Monthly Average limit is 37 lb/day and reported value was 113.03 lb/day at EFF-A. Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February. Violation U eSMR
1107795 07/31/2022 CAT1 Ammonia, Total (as N) Weekly Average limit is 3.5 mg/L and reported value was 6.93 mg/L at EFF-A. Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February. Violation U eSMR
1107796 07/31/2022 CAT1 Ammonia, Total (as N) Weekly Average limit is 82 lb/day and reported value was 140 lb/day at EFF-A. Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February. Violation U eSMR
1106722 06/29/2022 CAT1 Ammonia, Total (as N) 1-Hour Average (Mean) limit is 37 lb/day and reported value was 55.1 lb/day at EFF-A. To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average. The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers. Violation U eSMR
1106723 06/29/2022 CAT1 Ammonia, Total (as N) 1-Hour Average (Mean) limit is 82 lb/day and reported value was 91.46 lb/day at EFF-A. To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average. The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers. Violation U eSMR
1106724 06/29/2022 CAT1 Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 2.53 mg/L at EFF-A. To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average. The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers. Violation U eSMR
1106721 06/29/2022 CAT1 Ammonia, Total (as N) Weekly Average limit is 3.5 mg/L and reported value was 4.25 mg/L at EFF-A. To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average. The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers. Violation U eSMR
1100007 12/20/2021 CAT2 Cyanide, Total (as CN) Maximum Daily (MDEL) limit is 35 ug/L and reported value was 42 ug/L at EFF-A. Monitoring will continue Violation A eSMR
1100008 12/20/2021 CAT2 Cyanide, Total (as CN) Monthly Average limit is 17 ug/L and reported value was 42 ug/L at EFF-A. Will continue to monitor. Violation A eSMR
1080702 07/16/2020 DMON Permit requires quarterly monitoring of total hardness to be collected concurrently with the metals samples. Hardness at location RSW-001U (upstream Fancher) was inadvertently missed when metals were sampled for in July. There was no measurable flow in August and September to resample. New staff trained and QA/QC measures implemented. Violation U eSMR
1075218 04/28/2020 OEV Total Coliform Instantaneous Maximum limit is 240 MPN/100 mL and reported value was 1011.2 MPN/100 mL at UVS-001. Sample collection procedures have been reviewed with staff as a preventative measure. Violation U eSMR
1072140 02/20/2020 OEV Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .92 NTU at FIL-001. *** MMP Exempt Reason:Not an effluent violation. It is an other violation type and considered Order Condition violation. The high turbidity event may have been caused by the two membrane tanks being in standby for an extended period of time and not being recirculated prior to pumping to the filtrate header. A rung of programming code was found that could have potentially allowed filtration directly following an extended standby period. An inhibitor was previously added to the filtration logic code, but found that logic triggering "Normal Filtration" did not include the inhibitor. 5 minutes of standby has been added to the inhibitor code of the "Normal Filtration" logic to assure the filtrate pump will not run directly after an extended standby period unless 10 minute recirculation has completed. Violation B eSMR
1070175 12/12/2019 CTOX Chronic Toxicity Other limit is 1.3 TUc and reported value was 16 TUc at EFF-A. Given the high variability in both tests, we are requesting to repeat the study to confirm these findings. We will clean our effluent pipe after the UV. The study would then be repeated. It is anticipated the cleaning and repeat testing can be performed over the next 14 to 21 days. Violation U eSMR
1069801 12/11/2019 CAT2 Chlorine, Total Residual Instantaneous Maximum limit is .01 mg/L and reported value was .05 mg/L at EFF-A. *** MMP Exempt Reason:According to the discharger no chlorinated effluent was discharged from the facility. This is a violation of order condition not an effluent violation. A sample was taken from the recycled water tank at 9:46 AM and the result was <0.0015 mg/L . Please note that no chlorinated effluent was discharged from the facility. Violation B eSMR
1066104 09/14/2019 OEV Turbidity Instantaneous Maximum limit is 0.5 NTU and reported value was .5 NTU at FIL-001. *** MMP Exempt Reason:Not an effluent violation. It is an other violation type and considered Order Condition violation. A new SOP is being written to try to prevent this from happening in the future. Violation B eSMR
1064741 08/31/2019 CAT1 Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 6.5 mg/L at EFF-A. Changed the procedure when only one aeration basin is running Violation B eSMR
1064742 08/31/2019 CAT1 Ammonia, Total (as N) Monthly Average limit is 37 lb/day and reported value was 61 lb/day at EFF-A. Changed procedure when one aeration basin is running to prevent ammonia exceedances Violation B eSMR
1064743 08/09/2019 CAT1 Ammonia, Total (as N) Weekly Average limit is 3.5 mg/L and reported value was 30 mg/L at EFF-A. Changed procedure when one aeration basin is running to prevent ammonia exceedances Violation B eSMR
1064744 08/09/2019 CAT1 Ammonia, Total (as N) Weekly Average limit is 82 lb/day and reported value was 93 lb/day at EFF-A. Changed procedure when one aeration basin is running to prevent ammonia exceedances Violation U eSMR
1063141 07/31/2019 CAT1 Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 31 mg/L at EFF-A. Increasing the air to the basin and monitoring ammonia on site to have more timely results for process control. Violation B eSMR
1063137 07/31/2019 CAT1 Ammonia, Total (as N) Monthly Average limit is 37 lb/day and reported value was 135 lb/day at EFF-A. Increasing the air to the basin and monitoring ammonia on site to have more timely results for process control. Results from the lab typically take 10 business days Violation B eSMR
1063142 07/31/2019 CAT1 Ammonia, Total (as N) Weekly Average limit is 3.5 mg/L and reported value was 33 mg/L at EFF-A. Increasing the air to the basin and monitoring ammonia on site to have more timely results for process control. Results from the lab typically take 10 business days to receive. Violation B eSMR
1063144 07/30/2019 OEV Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .57 NTU at EFF-A. *** MMP Exempt Reason:Not an effluent violation. It is an other violation type and considered Order Condition violation. The lead will provide additional training to the operator emphasizing the importance of monitoring the SCADA. Violation B eSMR
1063138 07/26/2019 CAT1 Ammonia, Total (as N) Weekly Average limit is 82 lb/day and reported value was 377 lb/day at EFF-A. Increasing the air to the basin and monitoring ammonia on site to have more timely results for process control. Results form the lab typically take 10 business days to receive. Violation B eSMR
1063143 07/25/2019 OEV UV Banks in Operation Instantaneous Minimum limit is 25 % and reported value was 0 % at UVS-001. *** MMP Exempt Reason:Not an effluent violation. It is an other violation type and considered Order Condition violation. A coliform sample was collected at 10:29 am and the UV system was back on at 10:30 am. The membranes were then put back into filtration mode. Violation B eSMR
1063139 07/10/2019 OEV Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .57 NTU at EFF-A. *** MMP Exempt Reason:Not an effluent violation. It is an other violation type and considered Order Condition violation. To prevent this type of turbidity spike in the future at least one operator will be stationed at a workstation and watching to see if any strange or unauthorized commands are occurring while the programmer is working in the program. Violation B eSMR
1063140 07/06/2019 OEV Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .71 NTU at EFF-A. *** MMP Exempt Reason:Not an effluent violation. It is an other violation type and considered Order Condition violation. To prevent this type of turbidity spike in the future, two tanks will be placed in auto sequence off and two tanks in auto sequence available. Having two tanks auto sequence off will keep the same two membrane tanks running instead of the tanks rotating between filtration and stand-by. We will also investigate changing the SCADA program to have the tanks go into recirculation after coming out of standby to ensure turbidity is below 0.2 NTU before filtration mode is initiated. Violation B eSMR
Report displays most recent five years of violations. Refer to the Interactive Violation Report for more data.
Total Violations: 40 Priority Violations: 0
*Click the "(+/-) Violation Description" link to expand and contract the violation description.
*As of 5/20/2010, the Water Board's Enforcement Policy requires that all violations be classified as 1, 2 or 3, with class 1 being the highest. Prior to this, violations were simply classified as Yes or No. If a 123 classification has been assigned to a violation that occurred before this date, that classification data will be displayed instead of the Yes/No data.

Violation Types
CAT1 = Category 1 Pollutant (Effluent Violation for Group 1 Pollutant) CAT2 = Category 2 Pollutant (Effluent Violation for Group 2 Pollutant)
CTOX = Chronic Toxicity DMON = Deficient Monitoring
LREP = Late Report OEV = Other Effluent Violation

Expand/Contract Enforcement Actions
Enforcement Actions
Enf Id Enf Type Enf Order No. Effective Date Status
448748 Admin Civil Liability R5-2022-0501 08/02/2022 Active
443223 Staff Enforcement Letter null 01/28/2021 Historical
443221 Notice of Violation null 11/02/2020 Historical
432981 Staff Enforcement Letter null 07/12/2019 Historical
430241 Time Schedule Order R5-2019-0022 06/01/2019 Active
413288 Notice of Violation null 05/18/2017 Historical
392887 Oral Communication 08/21/2013 Historical
380889 Notice of Violation null 12/20/2011 Historical
376673 Staff Enforcement Letter null 12/03/2010 Historical
Total Enf Actions: 9

Expand/Contract Inspections
Inspections
Inspection ID Inspection Type Lead Inspector Actual End Date Planned Violations Attachment
47330313 B Type compliance inspection Hossein Aghazeynali 02/24/2022 N 0 Download
36863319 Complaint inspection Omar Mostafa 07/08/2019 N 0 Download
36847301 Complaint inspection Omar Mostafa 07/02/2019 N 0 Download
28539811 B Type compliance inspection Alexander Mushegan 05/10/2017 N 1 Download
20413852 B Type compliance inspection Alexander Mushegan 05/07/2015 N 1 Download
20401788 Complaint inspection Daniel Benas 08/04/2014 N 0 N/A
7471945 B Type compliance inspection Alexander Mushegan (Multiple) 03/09/2012 N 0 Download
4562581 B Type compliance inspection Carole Leong 05/25/2011 Y 2 [Attachments]
2354684 B Type compliance inspection Dennis Wilson (Multiple) 04/13/2010 Y 1 Download
Total Inspections: 9 Last Inspection: 02/24/2022
  
The current report was generated with data as of: 06/06/2024
Regional Boards are in the process of entering backlogged data.
As a result, data may be incomplete.