| Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
| 1159819 |
08/02/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 6.3 MPN/100 mL at UVS-001. |
The valve has been repaired, and the UV system is now operating correctly and do not anticipate any further issues caused by it. |
Violation |
U |
eSMR |
| 1159127 |
07/30/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 6.3 MPN/100 mL at UVS-001. |
The valve is now manually closed and is scheduled to be worked on again on 8/14/2026. UV train 2 will be monitored while on or verified that the valve is fully closed while off. |
Violation |
U |
eSMR |
| 1159129 |
07/29/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 6.3 MPN/100 mL at UVS-001. |
The valve is now manually closed and is scheduled to be worked on again on 8/14/2026. UV train 2 will be monitored while on or verified that the valve is fully closed while off.
|
Violation |
U |
eSMR |
| 1159125 |
07/28/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.1 MPN/100 mL at UVS-001. |
The valve is now manually closed and is scheduled to be worked on again on 8/14/2026. UV train 2 will be monitored while on or verified that the valve is fully closed while off.
|
Violation |
U |
eSMR |
| 1159126 |
07/26/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.1 MPN/100 mL at UVS-001. |
The valve is now manually closed and is scheduled to be worked on again on 8/14/2026. UV train 2 will be monitored while on or verified that the valve is fully closed while off. |
Violation |
U |
eSMR |
| 1159128 |
07/16/2026 |
Surface Water |
The violation occurred on July 16, 2026, due to a temperature difference greater than 5 degrees Fahrenheit between monitoring locations RSW 001U (67.6°F) and RSW 001D (76.3°F). The effluent temperature at EFF 001 was recorded as 86.2°F. However, flows at EFF 001 were 0.76 MGD, while flows in the receiving water (Fancher Creek) were recorded in excess of 200 MGD |
The City of Clovis will continue to monitor sampling practices to ensure accurate and representative reporting.
|
Violation |
U |
eSMR |
| 1155624 |
05/02/2026 |
Deficient Reporting |
Q1 2026. Missing Effluent and Receiving Water Characterization quarterly results. |
|
Violation |
B |
eSMR |
| 1154874 |
04/12/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 2.6 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues |
Violation |
B |
eSMR |
| 1154873 |
04/08/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.1 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues |
Violation |
B |
eSMR |
| 1154872 |
04/05/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 2.6 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues. |
Violation |
B |
eSMR |
| 1154875 |
04/02/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 4.1 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues. |
Violation |
B |
eSMR |
| 1154871 |
04/01/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 2.6 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues. |
Violation |
B |
eSMR |
| 1153747 |
03/11/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.0 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues. |
Violation |
B |
eSMR |
| 1153748 |
03/10/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.0 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues. |
Violation |
B |
eSMR |
| 1153749 |
03/09/2026 |
OEV |
Total Coliform 7-Day Median limit is 2.2 MPN/100 mL and reported value was 3.0 MPN/100 mL at UVS-001. |
All UV trains were due for cleaning in March. All UV trains were cleaning at the beginning of April 2026. We will continue to investigate the UV system and try to identify any possible issues. |
Violation |
B |
eSMR |
| 1155623 |
03/02/2026 |
DMON |
January 2026. Missing first week of RSW-001 monitoring. Also stated in cover letter. |
|
Violation |
B |
eSMR |
| 1155606 |
02/12/2026 |
Surface Water |
Dissolved oxygen was reduced below 5 mg/L. RSW-001U was 6.5 mg/L, RSW-001D was 4 mg/L. EFF-A daily average was 3.55 mg/L |
|
Violation |
B |
Report |
| 1155604 |
02/12/2026 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 63.7 Degrees F, RSW-001D was 74.9 Degrees F, EFF-002 was 72 Degrees F. |
|
Violation |
B |
Report |
| 1155605 |
02/05/2026 |
Surface Water |
Dissolved oxygen was reduced below 5 mg/L. RSW-001U was 7.5 mg/L, RSW-001D was 4.4 mg/L. EFF-A daily average was 3.2 mg/L |
|
Violation |
B |
Report |
| 1155603 |
02/05/2026 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 62.5 Degrees F, RSW-001D was 75.7 Degrees F, EFF-002 was 72 Degrees F. |
|
Violation |
B |
Report |
| 1155621 |
02/02/2026 |
DMON |
December 2025. Missing 4th week of RSW-001 monitoring. Also stated in the cover letter. |
|
Violation |
B |
eSMR |
| 1155622 |
02/02/2026 |
Deficient Reporting |
Q4 2025. According to the November 2025 report, the Effluent and Receiving Water Characterization Study monitoring was conducted in November and would be reported in the quarterly report. No data was reported. |
|
Violation |
B |
eSMR |
| 1155602 |
12/18/2025 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 50 Degrees F, RSW-001D was 68.2 Degrees F, EFF-002 was 74 Degrees F. |
|
Violation |
B |
Report |
| 1155601 |
12/11/2025 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 51 Degrees F, RSW-001D was 71.5 Degrees F, EFF-002 was 74 Degrees F. |
|
Violation |
B |
Report |
| 1155600 |
12/04/2025 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 50.9 Degrees F, RSW-001D was 75.6 Degrees F, EFF-002 was 74 Degrees F. |
|
Violation |
B |
Report |
| 1155599 |
07/31/2025 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 73.3 Degrees F, RSW-001D was 80.1 Degrees F, EFF-002 was 88 Degrees F. |
|
Violation |
B |
Report |
| 1146467 |
07/24/2025 |
DMON |
pH probe failed upon attempt to retrieve sample. |
The deficient probe was discarded and the City has purchased a new probe for monitoring. No other periods were missed on the weekly reporting. |
Violation |
U |
eSMR |
| 1146468 |
07/24/2025 |
DMON |
pH probe failed upon attempt to retrieve sample. |
The deficient probe was discarded and the City has purchased a new probe for monitoring. No other periods were missed on the weekly reporting. |
Violation |
U |
eSMR |
| 1139703 |
12/04/2024 |
DMON |
Contract laboratory Moore Twining Associates, Inc missed the hold time for Nitrite on December 4th , 2024 at 0845. The sample was delivered on December 4th at 1540. It was not analyzed until December 6th, 2024 at 1106 breaking the 48 hours hold time. |
A letter from Moore Twining Associates is included with cover letter of the SMR. |
Violation |
U |
eSMR |
| 1155594 |
10/31/2024 |
CAT2 |
Cyanide, Total (as CN) Monthly Average limit is 4.3 ug/L and reported value was 4.4 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1136729 |
10/04/2024 |
DMON |
the total coliform sample on 10/4/2024 was not checked within the method specific time frame resulting in an ambiguous result. The Coliform sample collected on 10/4/2024 was supposed to be readout on 10/5/2024. Unfortunately, the sample was not readout out until Monday morning 10/7/2024. Results of the sample were disqualified due to the broken readout time. |
Corrective taken to prevent this from happening again, If the lab technician is off then the operator is to send a picture of the results to the lab technician or PM. If the lab technician or PM do not receive the picture by 10am then they are to contact the operator and remind them to readout the coliform results. |
Violation |
U |
eSMR |
| 1132967 |
08/23/2024 |
OEV |
pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.36 SU at REC-001. *** MMP Exempt Reason:The provisions/requirements in subsections IV.C, V.B, and VI.C.8 are included to implement state law only. These provisions/requirements are not required or authorized under the federal CWA; consequently, violations of these provisions/requirements are not subject to the enforcement remedies that are available for NPDES violations. |
This was an isolated operator error, the operator has been retrained. |
Violation |
B |
eSMR |
| 1155620 |
08/02/2024 |
Deficient Reporting |
Q2 2024. Missing receiving water hardness. |
|
Violation |
B |
eSMR |
| 1131501 |
07/04/2024 |
DMON |
Recycle water was discharged to RSW-001 and weekly monitoring was not conducted at 001U/D. |
routine monitoring was missed due to the holiday. Training conducted with staff so that monitoring is rescheduled and not missed in the future. |
Violation |
U |
eSMR |
| 1155619 |
05/02/2024 |
Deficient Reporting |
Q1 2024. Missing receiving water hardness. |
|
Violation |
B |
eSMR |
| 1155578 |
04/30/2024 |
CAT2 |
Copper, Total Recoverable Maximum Daily (MDEL) limit is 4.8 ug/L and reported value was 8.2 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155577 |
04/30/2024 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 2.8 ug/L and reported value was 8.2 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155590 |
04/30/2024 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 37 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155618 |
04/02/2024 |
Deficient Reporting |
February 2024. Receiving water (RSW-002U/D) monitoring missing for week of 2/11-2/17 |
|
Violation |
B |
eSMR |
| 1155576 |
03/31/2024 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 2.8 ug/L and reported value was 4.8 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155589 |
03/31/2024 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 24 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1126885 |
03/29/2024 |
DMON |
RW discharge started at 001 on March 22, 2024. Weekly field observations conducted on March 29, 2024 were inadvertently conducted at 002U/D instead of 001U/D. |
Discussed with staff and the following weekly field observation was conducted at the correct discharge point, 001U/D. |
Violation |
U |
eSMR |
| 1126884 |
03/19/2024 |
OEV |
Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .76 NTU at FIL-001. |
The SOP on returning a membrane tank to normal filtration, as well as the permit limits, have been reviewed with the new operators. |
Violation |
U |
eSMR |
| 1155598 |
03/15/2024 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-002U was 61.7 Degrees F, RSW-002D was 68.2 Degrees F, EFF-002 was 74 Degrees F. |
|
Violation |
B |
Report |
| 1155597 |
03/08/2024 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-002U was 64.5 Degrees F, RSW-002D was 70.5 Degrees F, EFF-002 was 73.9Degrees F. |
|
Violation |
B |
Report |
| 1155575 |
02/29/2024 |
CAT2 |
Copper, Total Recoverable Monthly Average limit is 2.8 ug/L and reported value was 6.9 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1125395 |
02/23/2024 |
DMON |
TSS samples were collected and sent out to Moore Twining and Associates for analysis. The samples were not documented on the chain of custody, so the contract laboratory did not run the sample until after they were out of hold time. The results are documented on the SMR but out of hold time. |
Reviewed with operators and with lab. |
Violation |
U |
eSMR |
| 1155596 |
02/23/2024 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-002U was 58.5 Degrees F, RSW-002D was 64.2 Degrees F, EFF-002 was 73.4 Degrees F. |
|
Violation |
B |
Report |
| 1155574 |
02/07/2024 |
CAT2 |
Copper, Total Recoverable Maximum Daily (MDEL) limit is 4.8 ug/L and reported value was 6.9 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1125394 |
02/06/2024 |
OEV |
Turbidity Instantaneous Maximum limit is .5 NTU and reported value was .75 NTU at FIL-001. |
Programmer restored the 10 min re-circulation after a membrane tank has been in standby for 5 mins or more. It failed due to the outage on Jan 31, 2024. |
Violation |
U |
eSMR |
| 1124429 |
02/02/2024 |
LREP |
Once Only OneTime ( TECHRPT ) (Q4 2023 (MRP VII.B.1 Recycled Water User Summary Report) report for 2023/10/01 (2816152) was due on 01-FEB-24 |
|
Violation |
B |
Report |
| 1124737 |
01/31/2024 |
DMON |
The Clovis ST/WR Facility experienced a power outage on January 31st , 2024 causing the coliform
incubator to fall below acceptable temperature. This makes the results for Coliform invalid on January
31st, 2024. |
Power restored |
Violation |
U |
eSMR |
| 1155573 |
01/31/2024 |
CAT2 |
Copper, Total Recoverable Monthly Average (Mean) limit is 2.8 ug/L and reported value was 5 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155588 |
01/31/2024 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 30 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155572 |
01/03/2024 |
CAT2 |
Copper, Total Recoverable Maximum Daily (MDEL) limit is 4.8 ug/L and reported value was 5 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155587 |
12/31/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 32 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1123694 |
12/17/2023 |
OEV |
pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.49 SU at EFF-002. |
There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. |
Violation |
U |
eSMR |
| 1123697 |
12/15/2023 |
OEV |
pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.4 SU at EFF-002. |
There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. |
Violation |
U |
eSMR |
| 1123696 |
12/14/2023 |
OEV |
pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.44 SU at EFF-002. |
There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. |
Violation |
U |
eSMR |
| 1123695 |
12/13/2023 |
OEV |
pH Instantaneous Minimum limit is 6.5 SU and reported value was 6.43 SU at EFF-002. |
There is now 220 gallons of Sodium Hydroxide on site, and a bulk tank with continuous pH monitoring after UV disinfection and prior to entering the recycled water storage tank. |
Violation |
U |
eSMR |
| 1155586 |
11/30/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 30 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155595 |
11/03/2023 |
Surface Water |
Temperature was increased by more than 5 Degrees F. RSW-001U was 55.7 Degrees F, RSW-001D was 72.3 Degrees F, EFF-001 was 77.9 Degress F. |
|
Violation |
B |
Report |
| 1155585 |
10/31/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 33 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155584 |
09/30/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 29 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155583 |
07/31/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 27 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155570 |
06/30/2023 |
CAT2 |
Copper, Total Recoverable Monthly Average (Mean) limit is 2.8 ug/L and reported value was 3.2 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155582 |
06/30/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average (Mean) limit is 23 ug/L and reported value was 26 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155581 |
05/31/2023 |
CAT2 |
Zinc, Total Recoverable Monthly Average limit is 23 ug/L and reported value was 29 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155593 |
02/14/2023 |
CAT2 |
Cyanide, Total (as CN) Maximum Daily (MDEL) limit is 8.5 ug/L and reported value was 9.2 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1155568 |
01/31/2023 |
CAT2 |
Copper, Total Recoverable Monthly Average (Mean) limit is 2.8 ug/L and reported value was 3.4 ug/L at EFF-A. |
|
Violation |
B |
Report |
| 1109608 |
09/06/2022 |
DMON |
During the month of September 2022, we had our historian go down for a period of 6 days. We have been attempting to recover data from the PLC for dates 9/6-9/11/2022 but are unable to do so. The lost reportable data includes:
UV Transmittance Average
UV Transmittance Maximum
UV Dose Average
UV Dose Maximum
We have alarm histories that are accurate as well as daily documented values for each one of these data points that have been reported. It would be a one-time read instead of a 24-hour max or average value.
|
We have added an alarm into our SCADA call out system that will notify us if or when the historian goes down. In addition, We will be installing a stand-alone system as a backup to help prevent any future incidents of lost data. |
Violation |
U |
eSMR |
| 1109607 |
09/06/2022 |
DMON |
During the month of September 2022, we had our historian go down for a period of 6 days. We have been attempting to recover data from the PLC for dates 9/6-9/11/2022 but are unable to do so. The lost reportable data includes:
1. Combined Filtrate Tubidity Maximum
2. Combined Filtrate Tubidity Average
We have alarm histories that are accurate as well as daily documented values for each one of these data points that have been reported. It would be a one-time read instead of a 24-hour max or average value. |
We have added an alarm into our SCADA call out system that will notify us if or when the historian goes down. In addition, we will be installing a stand-alone system as a backup to help prevent any future incidents of lost data. |
Violation |
U |
eSMR |
| 1107793 |
07/31/2022 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 5.65 mg/L at EFF-A. *** MMP Exempt Reason:Older than 3 years. |
. Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February. |
Violation |
B |
eSMR |
| 1107794 |
07/31/2022 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 37 lb/day and reported value was 113.03 lb/day at EFF-A. *** MMP Exempt Reason:Older than 3 years. |
Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February.
|
Violation |
B |
eSMR |
| 1107795 |
07/31/2022 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 3.5 mg/L and reported value was 6.93 mg/L at EFF-A. *** MMP Exempt Reason:Older than 3 years. |
Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February.
|
Violation |
B |
eSMR |
| 1107796 |
07/31/2022 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 82 lb/day and reported value was 140 lb/day at EFF-A. *** MMP Exempt Reason:Older than 3 years. |
Jacobs repaired the cap and the plumbing from the air header to the diffusers and unclogged a majority of the diffusers by Monday August 26th on both basins. We also planned a full diffuser replacement and overhaul of the diffusers for February/March 2023. The new diffusers are on order and will not be available until late January or early February.
|
Violation |
B |
eSMR |
| 1106722 |
06/29/2022 |
CAT1 |
Ammonia, Total (as N) 1-Hour Average (Mean) limit is 37 lb/day and reported value was 55.1 lb/day at EFF-A. |
To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average.
The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers.
|
Violation |
U |
eSMR |
| 1106723 |
06/29/2022 |
CAT1 |
Ammonia, Total (as N) 1-Hour Average (Mean) limit is 82 lb/day and reported value was 91.46 lb/day at EFF-A. |
To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average.
The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers.
|
Violation |
U |
eSMR |
| 1106724 |
06/29/2022 |
CAT1 |
Ammonia, Total (as N) Monthly Average limit is 1.6 mg/L and reported value was 2.53 mg/L at EFF-A. *** MMP Exempt Reason:Older than 3 years. |
To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average.
The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers.
|
Violation |
B |
eSMR |
| 1106721 |
06/29/2022 |
CAT1 |
Ammonia, Total (as N) Weekly Average limit is 3.5 mg/L and reported value was 4.25 mg/L at EFF-A. |
To prevent further exceedances, Jacobs is running the centrifuge longer hours but at a lower flow rate. We have turned on our third aeration blower and are running it at 100%. In addition to the longer run hours and third blower running the City of Clovis has reduced flows to the facility down to 1.6 MGD as a daily average.
The Centrifuge is scheduled to be repaired early August. While the centrifuge is being repaired, we will have a belt press rental on site to prevent excessive inventory in our aeration basins. Jacobs and the City of Clovis will collaborate together and determine the best time to repair the diffusers.
|
Violation |
U |
eSMR |
| 1100007 |
12/20/2021 |
CAT2 |
Cyanide, Total (as CN) Maximum Daily (MDEL) limit is 35 ug/L and reported value was 42 ug/L at EFF-A. |
Monitoring will continue |
Violation |
A |
eSMR |
| 1100008 |
12/20/2021 |
CAT2 |
Cyanide, Total (as CN) Monthly Average limit is 17 ug/L and reported value was 42 ug/L at EFF-A. |
Will continue to monitor. |
Violation |
A |
eSMR |
|