Violation ID |
Occurred Date |
Violation Type |
(-) Violation Description |
Corrective Action |
Status |
Classification |
Source |
1141739 |
02/28/2025 |
DMON |
Operations staff attempted to record a dissolved oxygen value using Hach HQ40d which displayed an error code. Staff did not retry and failed to record a reportable value for emergency storage pond 7 for the second, third, and final week of February and failed to record a reportable value for emergency storage pond 2 during the second week of February. |
We performed the corrective action by retraining the entire operations team on pond monitoring requirements as found in the NPDES permit on March 26th, 2025. |
Violation |
B |
eSMR |
1136569 |
10/11/2024 |
DMON |
The laboratory staff member responsible for performing weekly EFF-001 sampling began an indefinite leave on October 11, 2024. Weekly EC samples were missed while acclimating to their departure. |
The facility has chosen to restructure the sampling and analysis procedures such that WWTP operators are assisting laboratory personnel with non-regulatory sampling. The Facility has also reduced the amount of sampling needed for process control data collection. These temporary accommodations made by operations personnel will allow the remaining laboratory staff to focus on regulatory sampling while adjusting to the decrease in laboratory staffing. The corrective action was implemented on October 22, 2024. |
Violation |
U |
eSMR |
1131431 |
07/17/2024 |
Surface Water |
Turbidity samples collected at RSW-001 and RSW-002 on July 17 resulted in a 1.1 NTU difference exceeding the 1 NTU receiving water limitation (Section V.A.18.b.). |
Operators will monitor turbidity readings from the chlorine contact basin and reduce flows through the filters if elevated readings are observed. Excess discharged will be conveyed to a storage pond. |
Violation |
U |
eSMR |
1139241 |
02/04/2024 |
Other Water Code Sections |
Failure to provide a report of waste discharge 180 days in advance of the discharge of waste is a violation of CWC Section 13376. |
The Discharger has made modifications to the influent pump stations to prevent similar spills from occurring in the future. |
Violation |
B |
Report |
1139242 |
02/04/2024 |
Order Conditions |
Violation of R5-2022-0040 Discharge Prohibition III.A. |
The Discharger has made modifications to the influent pump stations to prevent similar spills from occurring in the future. |
Violation |
B |
Report |
1139243 |
02/04/2024 |
Order Conditions |
Violation of R5-2022-0040 Discharge Prohibition III.B. |
The Discharger has made modifications to the influent pump stations to prevent similar spills from occurring in the future. |
Violation |
B |
Report |
1124345 |
01/29/2024 |
OEV |
Total Coliform 7-Day Median limit is 23.0 MPN/100 mL and reported value was 70.0 MPN/100 mL at EFF-001. |
Operators will replace the nylon nipple at Eff-001 as needed to ensure a more representative sample in the future. |
Violation |
B |
eSMR |
1122105 |
10/11/2023 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 0.52 mg/L at EFF-001. |
The programmed automatic chlorine meter bump tests have been removed. Instead an operator will manually bump test the chlorine meters. This means an operator will be present to visually assure that no chlorinated effluent will be discharged during a bump test. |
Violation |
B |
eSMR |
1121283 |
09/20/2023 |
DMON |
Dissolved Oxygen and Turbidity were not sampled a second time in this monitoring period. Laboratory staff forgot to complete monitoring. |
Laboratory Supervisor and Chief Plant Operator will review data entered on a weekly basis to verify that all required monitoring is being completed. |
Violation |
U |
eSMR |
1121284 |
09/20/2023 |
DMON |
pH, Temperature, Dissolved Oxygen and Turbidity were not sampled a second time in this monitoring period. Laboratory staff forgot to complete monitoring. |
Laboratory Supervisor and Chief Plant Operator will review data entered on a weekly basis to verify that all required monitoring is being completed. |
Violation |
U |
eSMR |
1120789 |
08/31/2023 |
CAT2 |
Chlorine, Total Residual 1-Hour Average (Mean) limit is 0.019 mg/L and reported value was 0.91 mg/L at EFF-001. |
In the future, prior to accessing the programming (Programmable Logic Controllers or SCADA) involving the chemical dosing systems, the pond 6 gate valve will be opened, diverting effluent flow from the river to Emergency Retention Basin 6. This will eliminate the possibility of any control glitches causing an Effluent violation. |
Violation |
B |
eSMR |
1125480 |
05/01/2023 |
LREP |
Annual SMR ( MONNPDES ) (Recycled Water Policy Annual Report) report for 2022 (2830865) was due on 30-APR-23 |
|
Violation |
B |
Report |
1112496 |
12/27/2022 |
OEV |
Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 33 MPN/100 mL at EFF-001. |
In the future plant operators will consider increasing the feed of disinfection agent when abrupt increases in flow cause the effectiveness of the filtration process to decrease. |
Violation |
U |
eSMR |
1109450 |
09/30/2022 |
CAT2 |
Dichlorobromomethane Monthly Average limit is 16 mg/L and reported value was 18.7 mg/L at EFF-001. |
Operations staff decreased Chlorine dosing last month. The first sample taken on September 9, 2022 remained above the AMEL. In response to this operations staff adjusted the operation schedule for the cloth media filters, increasing the number of filter backwash cycles, which should lower the amount of organic solids that are present at the time of chlorine introduction. Which should decrease the formation of Dichlorobromomethane. |
Violation |
U |
eSMR |
1108556 |
08/31/2022 |
CAT2 |
Dichlorobromomethane Monthly Average (Mean) limit is 16 mg/L and reported value was 18.3 mg/L at EFF-001. |
Operations staff has lowered the Chlorine does to decrease the occourance of Dichlorobromomethane. |
Violation |
B |
eSMR |
1104332 |
04/11/2022 |
OEV |
Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 176 MPN/100 mL at EFF-001. |
In response operations staff reviewed disinfection parameters and found no indicators for the exceedance. Sampling and analysis methods were reviewed and a duplicate sample was sent to contract laboratory to verify the accuracy of testing. |
Violation |
U |
eSMR |
1104333 |
04/05/2022 |
OEV |
Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 177 MPN/100 mL at EFF-001. |
In response operations staff reviewed disinfection parameters and found no indicators for the exceedance. Sampling and analysis methods were reviewed and a duplicate sample was sent to contract laboratory to verify the accuracy of testing. |
Violation |
U |
eSMR |
1099212 |
12/13/2021 |
OEV |
Total Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 32 MPN/100 mL at EFF-001. |
Chemical disinfection dosing was adjusted to compensate for the increased effluent flow volume as well as higher TSS within the effluent. |
Violation |
U |
eSMR |
1096464 |
11/01/2021 |
LREP |
Once Only OneTime ( TECHRPT ) (Salinity Eval and Min Plan) report for 2017/04/01 (2394577) was due on 31-OCT-21 |
|
Violation |
B |
Report |
1087892 |
02/16/2021 |
OEV |
Fecal Coliform 7-Day Median limit is 23 MPN/100 mL and reported value was 802 MPN/100 mL at EFF-001. |
Laboratory and Operations staff were trained on proper coliform sampling. The standard operation procedure for coliform sampling has been updated to state that samples should not be taken during non-representative times. Also the configuration of the coliform sample point has been changed so that it is not downstream of these valves. |
Violation |
U |
eSMR |