Violation ID |
Violated Order |
Violation Type |
Date |
(+) Description |
Corrective Action |
Source |
Classification/Priority |
Facility ID |
Facility Name |
139607 |
R9-2000-0177 |
Reporting |
02/15/1997 |
IN JAN-DEC 96 THE EFFLUENT MONITORING FOR ARSENIC AND MERCURY WAS NOT SUBMITTED |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
139762 |
R9-2000-0177 |
Other Effluent Violation |
08/21/1997 |
COMPOSITE SAMPLER ONLY COLLECTING EFFLUENT SAMPLES FROM CLARIFIER NO.3 INSTEAD O |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140206 |
R9-2000-0177 |
Other Effluent Violation |
02/28/1992 |
IN JANUARY 1992: 1 OF 1 EFFLUENT TDS, 1 OF 1 EFFLUENT SULFATE AND 1 OF 1 EFFLUE |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140207 |
R9-2000-0177 |
Reporting |
02/28/1992 |
IN JANUARY 1992: THE REPORT WAS INCOMPLETE. THE SEWAGE SOLIDS LOG WAS MISSING. |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
140208 |
R9-2000-0177 |
Reporting |
02/28/1992 |
IN JANUARY 1992: THE REPORT WAS INCOMPLETE. THE FLOW TO SPRAY FIELDS WAS NOT G |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
140290 |
R9-2000-0177 |
Other Effluent Violation |
01/30/1992 |
IN THE DECEMBER 1991 REPORT: THE EFFLUENT TDS AND SULFATE VALUES EXCEEDED THE L |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140291 |
R9-2000-0177 |
Reporting |
01/30/1992 |
IN THE OCTOBER-DECEMBER 1991 REPORT: THE SANTA MARIA CREEK MONITORING DATA WAS |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
140431 |
R9-2000-0177 |
Reporting |
03/11/1992 |
SAMPLES BASED ON GRAB SAMPLES INSTEAD OF 24 HOUR FLOW PROPORTIONAL COMPOSITE SAM |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
140442 |
R9-2000-0177 |
Other Effluent Violation |
04/30/1992 |
IN MARCH 1992: 1/1 EFFLUENT TDS AND 1/1 EFFLUENT SULFATE VALUES EXCEEDED THE LI |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140443 |
R9-2000-0177 |
Other Effluent Violation |
03/30/1992 |
IN FEBRUARY 1992: 1/1 EFFLUENT TDS VALUE, 1/1 EFFLUENT SULFATE VALUE, AND 1/1 E |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140900 |
R9-2000-0177 |
Reporting |
09/30/1992 |
IN AUGUST 1992: THE SEWAGE SOLIDS LOG WAS MISSING FROM THE REPORT. |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
140940 |
R9-2000-0177 |
Other Effluent Violation |
09/30/1992 |
IN AUGUST 1992: 1 OF 1 EFFLUENT TDS VALUE EXCEEDED THE 30-DAY AVERAGE LIMIT AND |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140948 |
R9-2000-0177 |
Other Effluent Violation |
07/30/1992 |
IN JUNE 1992: 1 OF 1 EFFLUENT TDS VALUE AND 1 OF 1 EFFLUENT SULFATE VALUE EXCEE |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
140952 |
R9-2000-0177 |
Other Effluent Violation |
08/30/1992 |
IN JULY 1992: 1 OF 1 TDS VALUE EXCEEDED THE LIMITS. 1 OF 1 SLUFATE VALUE EXCEE |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141174 |
R9-2000-0177 |
Other Effluent Violation |
10/30/1992 |
IN SEPTEMBER 1992: 1 OF 1 EFFLUENT TOTAL DISSOLVED SOLIDS VALUE, 1 OF 1 EFFLUEN |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141238 |
R9-2000-0177 |
Other Effluent Violation |
11/30/1992 |
IN OCTOBER 1992: 1 OF 1 EFFLUENT CHLORIDE VALUE EXCEEDED THE 30-DAY AVERAGE LIM |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141393 |
R9-2000-0177 |
Other Effluent Violation |
02/28/1993 |
IN JANUARY 1993: 2 OF 4 EFFLUENT BOD VALUES, 2 OF 4 EFFLUENT TSS VALUES, 1 OF 1 |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141394 |
R9-2000-0177 |
Other Effluent Violation |
01/30/1993 |
IN DECEMBER 1992: 1 OF 1 EFFLUENT TDS VALUE EXCEEDED THE 30-DAY AVERAGE LIMIT. |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141645 |
R9-2000-0177 |
Unauthorized Discharge |
02/25/1993 |
NO INFLUENT FLOW ENTERING THE TREATMENT PLANT DUE TO BROKED SEWER MAIN TRUNK LIN |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
141718 |
R9-2000-0177 |
Other Effluent Violation |
03/30/1993 |
IN FEBRUARY 1993: 1 OF 1 EFFLUENT BOD VALUE AND 1 OF 1 EFFLUENT TDS VALUE EXCEE |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141912 |
R9-2000-0177 |
Other Effluent Violation |
07/30/1993 |
IN THE APRIL AND JUNE REPORTS THE TURBIDITY VALUES WERE EXCEEDED. |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141953 |
R9-2000-0177 |
Other Effluent Violation |
07/31/1993 |
APRIL-JUNE 93: 29 OF 30 TURBIDITY VALUE WERE EXCEEDED. 1 OF 1 TDS EXCEEDED THE L |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
141954 |
R9-2000-0177 |
Reporting |
07/31/1993 |
APRIL-JUNE 93: MAP OF CREEK SAMPLES MISSING |
|
Undetermined |
N |
255679 |
Santa Maria WWTP |
146836 |
R9-2000-0177 |
Other Effluent Violation |
08/31/1993 |
JULY 93: 3 OF 3 COLIFORM VALUES EXCEEDED THE LIMIT. 1 OF 1 SULFATE CALUE EXCEE |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
147204 |
R9-2000-0177 |
Other Effluent Violation |
08/30/1993 |
IN JULY 1993: 1 OF 1 TDS VALUE EXCEEDED THE LIMIT. 1 OF 1 COLIFORM VALUE EXCEE |
|
Undetermined |
Y |
255679 |
Santa Maria WWTP |
Violation ID: An auto-generated unique identifier. Violations from our SMARTS database have a leading "S." |
Violated Order: This is the Board Order related to the instance of noncompliance. |
Violation Type: This is used to differentiate violations by the use of categories. Violations coming from our SMARTS database have "SW" in the type name. |
| Deficient Monitoring | Monitoring is missing or incorrect in some way, such as incorrect analysis method, wrong sampling location, QA/QA criteria not met, etc. |
| Basin Plan Prohibition | Violation of a Basin Plan prohibition not in the permit (e.g., discharge to prohibited zone, etc.) |
| Best Management Practice (BMP) | BMPs not maintained, deficient, or not implemented. Also "SW - Deficient BMP Implementation." |
| Enforcement Action | Enforcement Action is violated (e.g., if interim limits in a Time Schedule Order are exceeded). |
| Fees | Annual fees not paid on time or in full. |
| SW - Failure to Obtain Permit | Failure to obtain coverage under the appropriate storm water NPDES permit. |
| SW - Unauthorized NSWD | A non-storm water discharge with the appropriate permit/WDRs or without coverage under a General Order or discharges not covered by the discharger's Order |
| Order Conditions | Violations of prohibitions, provisions, and maintenance-type requirements (e.g., pond freeboard) contains in the permit/WDRs. |
| Pretreatment | Failure to adequately implement the pretreatment program. |
| SW - Incomplete/Insufficient SWPPP | Storm Water Pollution Prevention Plan (SWPPP) not on site or not implemented. |
| Unauthorized Discharge | Dischargers without permit/WDRs or without coverage under a General Order or discharges not covered by the discharger's Order |
| Deficient Reporting | Incomplete report or failing to notify Water Board of violations |
| Failure to Notify | Failure to notify the Water Board of a spill within a defined period of time. |
| Late Report | Report is not received or received after its due date. |
| Acute Toxicity (ATOX) | Violation of an acute toxicity effluent limit. |
| Chronic Toxicity (CTOX) | Violation of an chronic toxicity effluent limit. |
| Category 1 (CAT1) | Violation of an effluent limiation for a Group II Pollutant (e.g., chlorine, copper, cyanide, etc.). A full list is available in Appendix D of the current Enforcement Policy. |
| Category 2 (CAT2) | Violation of an effluent limiation for a Group I Pollutant (e.g., BOD, TSS, nitrate, etc.). A full list is available in Appendix C of the current Enforcement Policy. |
| Other Effluent Violation (OEV) | Violation of any constituent-specific effluent limit not included in Group I or II (e.g., pH, turbidity, temperature, coliform, etc.) |
| Receiving Water - Groundwater | Violation of receiving water limit where discharge is to surface water. |
| Receiving Water - Surface Water | Violation of receiving water limit where discharge is to groundwater. |
| Hydromodification | Noncompliance with dredge and fill requirements. |
| Sanitary Sewer Overflow/Spill | Discharge from collection system (except private laterals); other spills and/or bypassing of treatment unit(s). |
Date: This is the date the violation occurred. |
Status: Depending on which report the user is viewing, this will either be "violation" or "dismissed." Dismissed violation were at one time believed to be violations (or system-generated), but were later dismissed by Water Board staff. |
Description: This is the description of the violation and can be either inputed manually or by the system. |
Source: This is where or how the violations was determined (e.g., inspection, report, complaint, etc.) |
More information about violations can be found in the Water Quality Enforcement Policy |