Violation ID |
Occurrence Date |
Violation Type |
Violation Description(-) |
Violation Status |
Priority |
Source |
Facility Name |
Violated Reg. Meas. ID |
Violated Reg. Meas. Order No. |
Linked to Enf. |
1127444 |
03/05/2024 |
CAT1 |
Chloride Daily Maximum limit is 150 mg/L and reported value was 169 mg/L at EFF001 WRR. |
Violation |
N |
eSMR |
Pomona Water Reclamation Plant |
134831 |
81-034 |
N |
1125030 |
01/04/2024 |
Deficient Monitoring |
Per Section I of the MRP, recycled water samples shall be analyzed daily for total coliform. The total coliform result in the recycled water sample collected on January 4 was invalidated due to a laboratory error in which the analyst left the bacterial culture tubes outside of the incubator after the 24-hours read time. All other coliform results for the month were either non-detect or 1 CFU/100 mL, therefore, this result was expected to be within normal ranges. Laboratory staff were reminded of proper procedures. |
Violation |
N |
eSMR |
Pomona Water Reclamation Plant |
134831 |
81-034 |
N |
1125029 |
01/08/2024 |
Order Conditions |
An unauthorized recycled water discharge of a maximum of 9,000 gallons occurred on January 8 from roughly 7:10 a.m. to 7:30 a.m. at the Sanitation Districts' Spadra Landfill located at 4125 West Valley Boulevard in the city of Walnut. The Sanitation Districts notified the Regional Board at 3:45 p.m. on January 8, with a follow up letter on January 12. The unauthorized discharge originated from a below-grade recycled water distribution line near Bench 5 of the landfill on the southwestern side of the facility. The discharge occurred due to a crack in a Victaulic pipe connection fitting which allowed the line to separate, discharging recycled water into the soil. The pipe separation led to surface runoff downslope and into the storm drain prior to the pipeline being isolated. The leak was observed at approximately 7:10 a.m. on January 8, and continued until approximately 7:30 a.m. the same day, when site staff isolated the line. Recycled water was discharged into the soil until it became saturated, emanated from the surface and began to flow approximately 400 feet down the bench road before entering a catch basin. The discharge then flowed another approximately 600 feet before entering a Los Angeles County Department of Public Works storm drain. This storm drain ultimately discharges into the San Jose Creek. The recycled water produced at the Pomona WRP is suitable for discharge to the San Jose Creek per its National Pollutant Discharge Elimination System permit (Order No. R4-2021-0097), therefore no impacts to public health or the environment are expected. Staff reported that there was little flow in the San Jose Creek channel and there were no indications that fish or wildlife had been adversely impacted; therefore, there were no observed biological impacts from the discharge. To minimize reoccurrence of similar events, the Sanitation Districts will investigate the installation of above-grade recycled water lines and initiate a Victaulic fitting inspection program. |
Violation |
N |
eSMR |
Pomona Water Reclamation Plant |
134831 |
81-034 |
N |
1122428 |
10/11/2023 |
Deficient Monitoring |
Per Section I of the MRP, recycled water samples shall be analyzed daily for total coliform. The total coliform result in the recycled water sample collected on October 11 was invalidated because of improper sample incubation procedure. The analyst failed to write down the read time on the lab bench sheet and was unable to verify the correct duration of the incubation period. Throughout the month, the coliform results were typically non-detectable, except for five separate instances in which it was recorded at 1 CFU/100mL. Therefore, this result was expected to be within normal range and in compliance with the WRRs. To prevent a recurrence of this issue, Laboratory staff will double check that the sample data is properly filled out on the bench sheet. |
Violation |
N |
eSMR |
Pomona Water Reclamation Plant |
134831 |
81-034 |
N |
1121729 |
08/09/2023 |
Groundwater |
Gross Alpha Violation, McCormick Farms Control Well. Sampled on 8/9/23, 70.1+-2.707pCi/L |
Violation |
N |
eSMR |
Camarillo WRP |
393691 |
R4-2013-0140 |
N |
1121728 |
08/09/2023 |
Groundwater |
Managense Violation on Las Posas Control Well. 240ug/L. |
Violation |
N |
eSMR |
Camarillo WRP |
393691 |
R4-2013-0140 |
N |
1121727 |
08/09/2023 |
Groundwater |
Manganese Violation for Camarillo Springs Control Well. 510ug/L. |
Violation |
N |
eSMR |
Camarillo WRP |
393691 |
R4-2013-0140 |
N |
1121726 |
08/09/2023 |
Groundwater |
Uranium Violation on McCormick Farms Well. Sampled on 8/9/23, 99pCi/L. |
Violation |
N |
eSMR |
Camarillo WRP |
393691 |
R4-2013-0140 |
N |
1121673 |
09/23/2023 |
Deficient Monitoring |
Per Section I of the MRP, recycled water samples shall be analyzed daily for total coliform. The total coliform result in the recycled water sample collected on September 23 was invalidated because of improper sample incubation procedure. Throughout the month, the coliform results were typically non-detectable, except for one instance in which it was recorded at 2 CFU/100 mL and three other separate instances where it was recorded at 1 CFU/100 mL. Therefore, this result was expected to be within normal range. To prevent a recurrence of this issue, Laboratory senior staff revisited the procedure with the analyst. |
Violation |
N |
eSMR |
Pomona Water Reclamation Plant |
134831 |
81-034 |
N |
1120968 |
08/21/2023 |
Deficient Monitoring |
Per Section I of the MRP, recycled water samples shall be analyzed daily for total coliform. The total coliform result in the recycled water sample collected on August 21 was invalidated because the bacterial plate was discarded by the lab analyst before confirming two colonies. All other coliform results for the month were either non-detect or, in one occurrence, 2 CFU/100 mL, therefore, this result was expected to be within normal ranges. To prevent a recurrence of this issue, Laboratory senior staff revisited the procedure with the analyst. |
Violation |
N |
eSMR |
Pomona Water Reclamation Plant |
134831 |
81-034 |
N |
Report defaults to display violations within the last year. Click here to see last five years of violations. Refer to the Interactive Violation Report for more data.
|